7 Operation
38 of 80
KSB Delta Primo
1983.811/02-EN
7.9.5 Fire alert
The fire alert connection is an NC contact. When the contact is open, all pumps are
switched off in succession after a configurable start delay. An alert (red LED) is
output. In this case, the dry running protection and/or remote ON/OFF functions, if
enabled, are ignored.
When the contact closes, the pump sets will stop depending on demand. The alert is
cleared.
7.9.6 Setting the ambient temperature monitoring device (optional)
If the configurable ambient temperature value is exceeded, a warning message is
output. The ambient temperature can be read on the display.
The ambient temperature monitoring device cannot be used in combination with
digital inputs for remote reset, setpoint changeover and functional check run.
ü
The temperature sensor Pt1000 is fitted and electrically connected.
(
1. Call up parameter 3-3-4 (WSD).
2. Set the water flow detection on the accumulator to TEMPERATURE.
3. Call up parameter 3-4-4-3 (ambient temperature).
4. Set the temperature [°C].
7.9.7 Enabling digital inputs (optional)
NOTE
This function cannot be used in conjunction with ambient temperature monitoring.
ü
The accumulator’s water flow detection (WSD) function is deactivated.
ü
Logged in at Service level.
1. Call up parameter 3-3-4 (WSD).
2. Set water flow detection on accumulator to OFF.
ð
WSD inputs 1 to 3 are available.
The following functions can be assigned via the digital inputs:
▪
Remote reset
– Activated by pulse to terminals.
▪
Setpoint changeover (see parameter 3-5-9)
– Activated by closing the contact, de-activated by opening the contact.
▪
Functional check run
– Pulse-activated.