6 Commissioning/Start-up/Shutdown
28 of 80
KSB Delta Primo
1983.811/02-EN
6.2.4.2 Fluid temperature
Table 9:
Temperature limits of the fluid handled
Permissible fluid temperature
Value
Maximum
+60 °C
+25 °C to DIN 1988 (DVGW)
4)
Minimum
0 °C
6.2.5 Minimum flow rate
Table 10:
Minimum flow rate per pump in manual mode
Size
Minimum flow rate per pump
[l/h]
Movitec 2B
200
Movitec 4B
400
Movitec 6B
600
Movitec 10B
1100
Movitec 15B
1600
Movitec 25B
2800
Movitec 40B
4600
Movitec 60B
6100
Movitec 90B
8500
6.3 Shutdown
6.3.1 Measures to be taken for shutdown
1
Fig. 6:
Venting and draining the accumulator
1
Vent plug
ü
The pressure booster system has been switched off. (
1. Loosen vent plug 1 at the accumulator.
ð
The pressure booster system is being vented and drained.
2. Re-tighten vent plug 1 on the accumulator.
6.3.2 Shutdown
Standard design
1. Set the master switch to 0.
Additional instruments
1. Set manual-0-automatic selector switch to 0.
4)
Applies to the handling of drinking water (Germany only)