EN

 

10 

•   Unscrew and remove the ionisation electrode (6); 
•   Undo the screws that secure the combustion head (3) 

to the combustion chamber (1); 

•  Remove the three screws on the burner head plate 

and change the diffusion ring securing it in such a way 
that the ignition electrode is equidistant between the 
two subsequent holes; 

•   Calibrate the gas pressure switch (4) on the gas valve group 

(Fig.3): 

•  Regulate the gas pressure switch to a value equal to 

80% the supply pressure; 

•  Regulate the pressure regulator for the gas valve group 

(Fig.3); to the burner pressure stated in Tab. I.: 

•  Connect a gauge to the pressure intake (1) upstream 

and a second gauge to the pressure intake 
downstream (2) of the valve group; 

•   Start the heater and take the reading off the 1st supply 

pressure gauge and if necessary adjust the pressure 
regulator (3) for the gas supply system until the correct 
supply pressure shown in Tab. I is reached; 

•  Take a reading off the 2nd working pressure gauge 

and if necessary use a screwdriver to adjust the 
pressure of the gas valve group (4) to restore the 
working pressure shown in Tab. I 

•   Apply the adhesive label with the words “SET UP FOR …” 

corresponding to the type of fuel and the category chosen 
on the gas valve group. 

 

OPERATING INSTRUCTIONS 

START-UP 

The heater works in “heating” mode, turning the switch (9) to  

 . 

To start the space heater (Fig. 1): 
•   Make sure the switch (9) is set to “0”; 
•  Switch on power to the heater by means of the isolation 

switch on the power switchboard; 

•   Move the switch (9) to position  ; 
•   Operation will only be automatic if a thermostat or another 

control device is connected to the thermostat plug (10). 

•   If after these operations, the generator does not work, refer 

to the “FAULTS, CAUSES AND REMEDIES” section and 
find the cause. 

STOP 

To stop operation turn the switch (9) to “0” if operation is 

manual, or to room thermostat if operation is automatic. 

Lastly, close the gas supply stopcock and turn off the isolation 

switch. 

The flame goes out and the fan motor will continue to run until 

the combustion chamber has cooled down completely. 

The flame goes out and the fan motor continues to work 

according to the preset mode (timed post-ventilation or 
continuous post-ventilation). 

 
 

VENTILATION 

The heater can work in “ventilation” mode turning the switch 

(14) to 

 : the fan motor starts, while the burner is off. 

 

TRANSPORT AND HANDLING 

The space heater can be lifted up and suspended using the 

four anchor hooks provided in the casing. 

 
Warning 

Before moving the unit: 
•  Stop the machine as indicated in the “STOP” 

paragraph; 

•  Disengage the power supply by removing the 

plug from the power socket; 

•  Fully unscrew the fitting that connects the gas 

pipe to the heater; 

•   Wait until the heater has cooled down. 
 

Warning 

During transportation and/or storage, make sure 
the gas valve group and gas connection pipes are 
not knocked or damaged in any way. 

 
MAINTENANCE 

For proper working efficiency the fans, the combustion 

chamber and the burner must be cleaned periodically. 

 

Warning 

Before performing any maintenance operations: 
•  Stop the machine as indicated in the “STOP” 

paragraph; 

•  Disengage the power supply by removing the 

plug from the power socket; 

•   Close the gas supply stopcock; 
•   Wait until the heater has cooled down. 

 

The heater can be cleaned and washed with water. It is 

however necessary to ensure that: 

• the power lead is disconnected and unplugged from the 
power supply socket 
• all access panels have been completely closed 
• no water jets are used at a distance of less than 2 m 
• all parts of it are completely dry before plugging in the power 
lead again. 

 

Warning 

Cleaning the heater by the wrong procedures can 
cause 
damage to things and/or persons. 

 

Cleaning must be carried out by removing any foreign bodies 

from the fan suction grills. 
 

 

 
 

Содержание PE45

Страница 1: ...ATEUR D AIR CHAUD AU GAS NATUREL G P L GENERATORE D ARIA CALDA A GAS NATURALE G P L GENERADOR DE AIRE CALIENTE A GAS NATURAL G P L 0694BU2235 PE45 L L 166 00 KR BEDIENUNGSANLEITUNG INSTRUCTIONS MANUAL...

Страница 2: ...ON ELECTRODE ELE CTRODE ALLUMAGE ELETTRODO ACCENSIONE ELECTRODO DE ENCENDIDO 8 RESET KNOPF MIT KONTROLLAMPE RESET BUTTON WITH CONTROL LAMP BOUTON REARMEMENT AVEC LAMPE TEMOIN PULSANTE DI RIARMO PULSAD...

Страница 3: ...ACHEN UND ABHILFEN F r die Warmlufterzeuger ist das folgende Zubeh r erh ltlich a Programmieruhr oder Raumthermostat oder eine anderweitige elektromechanische Vorrichtung f r die automatische Start un...

Страница 4: ...Thermostatstecker 10 auszuf hren Den Stecker 10 von der Schaltanlage abziehen ffnen und die Br cke zwischen den Klemmen 2 und 3 des Steckers entfernen Das Verbindungskabel zum Thermostat an die Klemm...

Страница 5: ...r ber den Trennschalter an der Schaltanlage mit Strom versorgen Schalter 9 in die Position verstellen Der Betrieb ist nur dann automatisch wenn ein Thermostat oder eine andere Kontrolleinrichtung an d...

Страница 6: ...kontrollieren und f r die Regelung die entsprechende Abbildung und die Anweisungen aus diesem Handbuch beachten 1 DRUCKMESSPUNKT EINLASS 2 DRUCKMESSPUNKT AUSLASS 3 EINSTELLUNG DRUCKSTABILISATOR 4 GASV...

Страница 7: ...nicht versperrt sind Kontrollieren dass der Raum ausreichend bel ftet ist Kontrollieren dass die Warmluft ungehindert austreten kann Ausl sung des Sicherheitsthermostats wegen berhitzung der Brennkamm...

Страница 8: ...panel max distance 3 m useful for ceiling mounted installations or in restricted situations where access to the control panel is limited d anti condensation kit indispensable for installations under v...

Страница 9: ...tible The gas supply hose connection must be of suitable size and adequate for the type of system to be set up and must be effected by arranging the gas ramp as shown in Fig 2 the gas pipe 1 the cut o...

Страница 10: ...the switch 9 to 0 if operation is manual or to room thermostat if operation is automatic Lastly close the gas supply stopcock and turn off the isolation switch The flame goes out and the fan motor wi...

Страница 11: ...rring to the corresponding figure and to the instructions contained in this handbook for adjustment 1 PRESSURE CHECK INLET 2 PRESSURE CHECK OUTLET 3 PRESSURE REGULATOR 4 GAS SOLENOID GROUP 5 GAS PRESS...

Страница 12: ...t the suction and the flow grills are unobstructed Check that the room is well ventilated Check that the hot air can escape freely Safety thermostat tripped due to the combustion chamber overheating C...

Страница 13: ...ENT CAUSES ET SOLUTIONS Les g n rateurs d air chaud de la s rie GA N peuvent tre compl t s par toute une s rie d accessoires a Horloge programmateur ou thermostat d ambiance ou autre dispositif lectro...

Страница 14: ...ancher le c ble lectrique au thermostat sur les bornes 2 et 3 de la fiche du thermostat 10 Refermer la fiche et la rebrancher dans la prise du coffret lectrique Attention Ne jamais essayer de mettre e...

Страница 15: ...onctionner en mode chauffage en pla ant l interrupteur 9 sur la position Pour mettre le g n rateur en marche Fig 1 V rifier que l interrupteur 9 est bien sur la position 0 Alimenter l appareil en agis...

Страница 16: ...se reporter la figure correspondante et aux instructions fournies dans ce livret pour le r glage 1 PRISE DE PRESSION ENTR E 2 PRISE DE PRESSION SORTIE 3 R GLAGE STABILISATEUR DE PRESSION 4 GROUPE LEC...

Страница 17: ...ifier que les grilles de l aspiration et de l vacuation ne sont pas obstru es V rifier que le local est correctement a r Contr ler que l air chaud peut sortir librement Intervention du thermostat de s...

Страница 18: ...RU 18 EN 1596 2008 EN 12669 2003 G20 G25 G30 G31 I 3 I 4 LI LI 8 8 4 b c 3 d 8 4 5 1 500 1 5 T 1 5 3...

Страница 19: ...RU 19 EN 1596 2008 100 3 100 3 25 2 250 2 EN 12669 2003 m H07RN F 1 5 2 2 10 10 2 3 2 3 10 2 1 2 3 4 2 I...

Страница 20: ...RU 20 4 I2H G20 20 I B 60 SIT 840 SIGMA 4 2 I Honeywell Dungs I 3 1 3 I 6 3 1 4 3 80 3 I 1 2 3 I 4 I 1 9 0 9 10 9 0 9...

Страница 21: ...RU 21 2...

Страница 22: ...RU 22 1 2 3 4 5 3 SIT 840 SIGMA 3 1 2 4 5...

Страница 23: ...RU 23 8 8...

Страница 24: ...nque sempre ricercare la causa che ha prodotto l intervento del dispositivo di sicurezza ed eliminarla prima di riavviare il generatore cfr INCONVENIENTI DI FUNZIONAMENTO CAUSE E RIMEDI I generatori d...

Страница 25: ...pina termostato 10 Rimuovere la spina 10 dal quadro elettrico aprirla e rimuovere il ponticello elettrico fra i morsetti 2 e 3 della spina Collegare il cavo elettrico di collegamento al termostato sui...

Страница 26: ...tore 9 in posizione Per avviare il generatore Fig 1 Assicurarsi che l interruttore 9 sia sulla posizione 0 Alimentare elettricamente il generatore agendo sull interruttore di sezionamento posto sul qu...

Страница 27: ...ento alla figura corrispondente e alle istruzioni contenute in questo libretto per la regolazione SIT 840 SIGMA 1 PRESA DI PRESSIONE IN ENTRATA 2 PRESA DI PRESSIONE IN USCITA 3 REGOLAZIONE STABILIZZAT...

Страница 28: ...mandata non siano ostruite Controllare che l ambiente sia ben aerato Controllare che l aria calda possa uscire liberamente Intervento del termostato di sicurezza per sovrariscaldamento della camera d...

Страница 29: ...gas al restablecerse la condici n faltante En los otros casos el funcionamiento s lo puede reanudarse presionando el pulsador de restablecimiento 8 o 4 seg n lo descrito en el apartado INCONVENIENTES...

Страница 30: ...las caracter sticas de la red el ctrica de alimentaci n se correspondan con las indicadas en la placa de identificaci n Atenci n La m quina dispone de un cable de alimentaci n provisorio utilizado pa...

Страница 31: ...esi n del quemador indicada en Tabla I Conectar un man metro a la toma de presi n 1 l nea arriba y un segundo man metro a la toma de presi n l nea abajo 2 del grupo v lvulas Poner en marcha el generad...

Страница 32: ...etamente cerrados no se hayan utilizado chorros de agua desde una distancia inferior a 2 m est completamente seco en todas sus partes antes de volver a conectar el cable de alimentaci n el ctrica Aten...

Страница 33: ...e impulsi n no est n obstruidas Controlar que el ambiente est adecuadamente ventilado Controlar que el aire caliente pueda salir libremente Intervenci n del termostato de seguridad por sobrecalentamie...

Страница 34: ...34 SCHALTSCHEMA WIRING DIAGRAM SCHEMA ELECTRIQUE SCHEMA ELETTRICO ESQUEMA ELETRICO...

Страница 35: ...IT CONTROLLO REMOTO BORNERA PARA CONEXI N KIT CONTROL REMOTO RP SET FERNBEDIENUNG BER BEDIENPANEEL KABEL L 5M KIT FOR REMOTE CONTROL FROM PANEL CABLE L 5M KIT CONTR LE DISTANCE PAR TABLEAU C BLE L 5 M...

Страница 36: ...36 45 kW Tab I...

Страница 37: ...E TEMP RATURE INCREMENTO DI TEMPERATURA INCREMENTO DE TEMPERATURA 8 NENNW RMELEISTUNG NOMINAL HEATING OUTPUT PUISSANCE THERMIQUE NOMINALE POTENZA TERMICA NOMINALE POTENCIA T RMICA NOMINAL 9 GEMESSENE...

Страница 38: ...9 G 30 BUTHANE CAT I 3B P Nenn Luftleistung Air output D bit d air Portata d aria Capacidad aire m 3 h 2500 Schutzart IP IP protection Protection IP IP Protezione IP Protecci n IP IP X4D Min Einsatz T...

Страница 39: ......

Страница 40: ...maintenance that is not effected according to the rules as asserted in the technical manual or unauthorized modifications on the original version as delivered from manufacturer leads to expiration of...

Отзывы: