4
ELECTRICAL CONNECTIONS
48
OPTISONIC 6400
www.krohne.com
08/2011 - 4000972602 - MA OPTISONIC 6400 R02 en
Current input active
•
U
int, nom
= 15 VDC
•
I
≤
22 mA
•
I
max
≤
26 mA (electronically limited)
•
U
0, min
= 19 V at I
≤
22 mA
•
no
no
no
no HART
®
•
Not galvanically isolated
•
X designates the connection terminals A or B, depending on the version of the signal
converter.
HART
®
connection active (point-to-point)
The parallel resistance to the HART
®
communicator must be R
≥
370
Ω
.
Figure 4-10: Current input active IIn
a
1
Signal
2
2-wire transmitter (e.g. temperature)
Figure 4-11: HART
®
connection active (I
a
)
1
HART
®
communicator