Installation and operating instructions
IFC 020
5/7
5.8 Status output S
Fct. 1.07 STATUS S
Press key
→
.
Select function of status outputs,
press
→
key
• ALL ERROR
(indicates all errors)
• FATAL.ERROR
(indicates fatal errors only)
• OFF
(switched off, no function)
• ON
(indicates that flowmeter is operative)
• F/R INDIC.
(indicates direction for current and pulse outputs, F/R mode)
• TRIP. POINT
(setting range: 002 – 115 PERCENT of Q
100%
, full-scale range)
Transfer to number setting with
↵
key, 1st digit (cursor) flashes.
Change flashing digit (cursor) with
↑
and
↓
keys. Use
→
and
←
keys to shift cursor 1 place to right or left.
Press
↵
key to return to Fct. 1.07 STATUS S.
• Characteristic of status output
Switch open
Switch closed
OFF
(switched off)
no function
ON
(e.g. operation indicator)
power OFF
power ON
F/R INDIC.
F
orward flow
R
everse flow
TRIP POINT
(limit switch)
inactive
active
ALL ERROR
(all errors)
errors
no error
FATAL.ERROR
(fatal errors only)
errors
no error
Please refer to Sect. 3.2 “factory settings”
Refer to Sect. 2.4 for connection diagrams, and to Sect. 5.14 for characteristics.