Unless otherwise provided by local regulations, the horizontal or vertical
terminal should be installed according to the following guidelines.
Fig. 7. Possible variants of the concentric air exhaust system output for the LEO
series devices
In the case of a chimney system outlet near a roof window
(A - B)
, the air intake must
be installed a minimum of 0.6 m above the top of the window. In addition, a distance
of 1 m - sides / top and 2 m - bottom should be kept between the chimney system and
the edge of the roof window. In the case of a standard roof-mounted window
(H)
, the
terminal may not be installed below its lower edge and at a distance of at least 1 m
from its sides. Other requirements are presented below.