the combustion chamber, the search located on the base of the burner, burner and
burner base from the device. The service technician will reinstall all these components
after completing service
.
Fig. 4. Installation of the gas controller and the receiver in the inspection door
Requirement for the installation of an inspection door
If an inspection box is installed (it can be installed, depending on the needs, on the left
or right of the body), at least 1 m of free space should be left for service purposes.
NOTE: the inspection door should not be installed higher than 25 cm above floor level
due to extreme heat inside the building.
Fireplace sellers / installers should consult their clients, their architects and / or interior
designers about the pros and cons of each service option to identify critical installation
requirements that could prevent or hinder servicing.
Ventilation grates
- are required for all LEO series models and must be considered
when designing the housing. This allows the heat exchange accumulated inside the
fireplace housing to be released into the room, which also helps to keep the fireplace
walls and the housing cool.
One of the grilles must be at the bottom and the other at the top of the fireplace casing,
so we recommend that the upper one is placed a minimum of 15 cm and a maximum
of 50 cm below the ceiling in the fireplace, and the lower one a minimum of 5 cm above
the floor but not higher than 10 cm below bottom edge of the cover. It can be placed
on the front, sides or back of the fireplace casing, as long as it is directed inwards and
not outwards.
The minimum active field required for the cross-section of ventilation grates in
the series is:
LEO 100
LEO 200
LEO 70
LEO 76/62 LEO 45/68
Inlet grate
800 cm
2
1300 cm
2
500 cm
2
700 cm
2
500 cm
2
Outlet grate 1000 cm
2
1600 cm
2
600 cm
2
900 cm
2
600 cm
2
These are the minimum required cross-sectional areas of the grates, but there are no
contraindications to make them larger. Ventilation grilles can be in the form of barrels
or grille with blinds. If you use blinds, make sure that the cross-sectional area of the
free space in between the grille with the blinds is equal to or greater than the minimum
required for the model.