Parameters
Operating manual INVEOR
73
34.226
Starting current
Unit: %
min: 5
max.: 1000
Parameter manual:
p. xy
Transfer status:
2
Def.: 25
own value
(
to be
entered!
)
Relationship to
parameter:
34.227
For synchronous motors only.
Here the current can be adjusted which was impressed in the motor before
starting the control. In % of nominal motor current.
34.227
Init time
Unit: s
min: 0
max.: 100
Parameter manual:
p. xy
Transfer status:
2
Def.: 0.25
own value
(
to be
entered!
)
Relationship to
parameter:
34.226
For synchronous motors only.
Here the time can be set in which the start up current 34.226 is impressed.
34.228 – 34.230
Startup procedure
Unit: integer
min: 0
max.: 1
Parameter manual:
p. xy
Transfer status:
2
Def.: 0
own value
(
to be
entered!
)
Relationship to
parameter:
For synchronous motors only.
By changing the startup procedure to “Controlled”, higher starting torques
can be achieved.
0 = regulated, the inverter switches directly to the controller after the
impression phase.
1 = controlled, after the impression phase the rotation field is increased by
the control with start ramp 34.229 up to start frequency 34.230, then
switched to the controller.
Содержание INVEOR MA
Страница 1: ...Operating manual INVEOR Betriebsanleitung_INVEOR_A5 indd 1 28 02 11 10 33...
Страница 91: ...Guidelines Norms and Standards Operating manual INVEOR 91...
Страница 92: ...Guidelines Norms and Standards 92 Operating manual INVEOR...
Страница 93: ...Guidelines Norms and Standards Operating manual INVEOR 93...