Parameters
Operating manual INVEOR
71
34.090
Speed control K
p
Unit: mA/rad/s
min: 0
max.: 10,000
Parameter manual:
p. xy
Transfer status:
2
def.: 150
own value (
to
be entered!
)
Relationship to
parameter:
The control boost of the speed control can be optimised here, if the
automatically determined results (of the motor identification) are insufficient.
34.091
Speed control T
n
Unit: s
min: 0
max.: 10
Parameter manual:
p. xy
Transfer status:
2
def.: 4
own value (
to
be entered!
)
Relationship to
parameter:
The reset time of the speed control can be optimised here, if the
automatically determined results (of the motor identification) are insufficient.
34.110
Slip trimmer
Unit:
min: 0
max.: 1.3
Parameter manual:
p. xy
Transfer status:
2
def.: 1
own value (
to
be entered!
)
Relationship to
parameter:
33,034
Only for asynchronous motors.
This parameter can be used to optimise or deactivate slippage
compensation.
0 = disable (performance as on the grid)
1 = compensation for slippage..
34.130
Voltage control reserve
Unit:
min: 0
max.: 2
Parameter manual:
p. xy
Transfer status:
2
def.: 0,95
own value (
to
be entered!
)
Relationship to
parameter:
Only for asynchronous motors.
This parameter can be used to adjust voltage output.
Содержание INVEOR MA
Страница 1: ...Operating manual INVEOR Betriebsanleitung_INVEOR_A5 indd 1 28 02 11 10 33...
Страница 91: ...Guidelines Norms and Standards Operating manual INVEOR 91...
Страница 92: ...Guidelines Norms and Standards 92 Operating manual INVEOR...
Страница 93: ...Guidelines Norms and Standards Operating manual INVEOR 93...