![Kostal INVEOR MA Скачать руководство пользователя страница 24](http://html1.mh-extra.com/html/kostal/inveor-ma/inveor-ma_operating-manual_1999368024.webp)
Installation
24
Operating manual INVEOR
8. Attach the engine wires in the correct circuit, see also Fig. 4. (torque: 3,0
Nm).
When installing the engine wires, ensure that all bolts on
the terminal board are used with the nuts provided, even
if the star point is not connected!
1
2
Fig. 6:
Electric jumper
9. If a motor PTC/Klixxon is available, wire the connection cables to terminals
T1 and T2 (1) (torque: 0.6 Nm).
Make sure during assembly that the connection cables
are not trapped.
If the motor has a temperature sensor, this has to be
connected to terminals T1 and T2 (1); this requires that
the electric jumper (2) fitted in the delivery state has to be
removed.
If the electric jumper is installed, the temperature of
the motor will not be monitored.
10.Plug the drive control onto the adapter plate and fasten it evenly using the
four lateral bolts (torque: 4.0 Nm).