Parameters
48
Operating manual INVEOR
1.130
Reference channel
Unit: integer
min: 0
max.: 10
Parameter manual:
p. xy
Transfer status:
2
def.: 0
own value (
to
be entered!
)
Relationship to
parameter:
3,062 to 3,069
Determines the source from where the reference is to be read.
0 = internal potentiometer
1 = analogue input 1
2 = analogue input 2
3 = MMI/PC
4 = SAS
6 = motorizes potentiometer
7= total analogue inputs 1 and 2
8 = PID preset reference mode (3,062)
9 = fieldbus
10 = reference from INVEOR Soft-PLC
1.131
Enable software
Unit: integer
min: 0
max.: 11
Parameter manual:
p. xy
Transfer status:
2
def.: 0
own value (
to
be entered!
)
Relationship to
parameter:
1,132
1,150
2,050
4,030
4,050
WARNING
The motor may start immediately, depending on the change made.
Selection of the source for the control release.
0 = digital input 1
1 = digital input 2
2 = digital input 3
3 = digital input 4
4 = analogue input 1 (has to be selected in parameter 4.030)
5 = analogue input 2 (has to be selected in parameter 4.050)
6 = fieldbus
7 = SAS
8 = digital input 1 right / digital input 2 left
1,150 must be set to “0”
9 = autostart:
10 = INVEOR Soft-PLC
11 = preset frequency input (all inputs which are selected in parameter 2,050)
The motor may start immediately if hardware is enabled (En.Hw. Fig. 8) and a
reference have been provided.
This cannot be prevented even with parameter 1,132.
Содержание INVEOR MA
Страница 1: ...Operating manual INVEOR Betriebsanleitung_INVEOR_A5 indd 1 28 02 11 10 33...
Страница 91: ...Guidelines Norms and Standards Operating manual INVEOR 91...
Страница 92: ...Guidelines Norms and Standards 92 Operating manual INVEOR...
Страница 93: ...Guidelines Norms and Standards Operating manual INVEOR 93...