![Kostal INVEOR MA Скачать руководство пользователя страница 60](http://html1.mh-extra.com/html/kostal/inveor-ma/inveor-ma_operating-manual_1999368060.webp)
Parameters
60
Operating manual INVEOR
5.3.8
Digital outputs
For digital outputs 1 and 2 (DOx display DO1/DO2)
4.150/4.170
DOx function
Unit: integer
min: 0
max.: 50
Parameter manual:
p. xy
Transfer status:
2
def.: 0
own value (
to
be entered!
)
Relationship to
parameter:
4,151/4,171
4,152/4,172
Selection of the process value to which the output should switch.
0 = not allocated / INVEOR Soft-PLC
1= DC bus voltage
2= line voltage
3= motor voltage
4= motor current
5= frequency feedback
6= –
7= –
8= IGBT temperature
9= internal temperature
10= error (NO)
11= inverted error (NC)
12= final release levels
13= digital input1
14= digital input 2
15= digital input 3
16= digital input 4
17= ready for operation
18= ready
19= operation
20= ready for ope ready
21= ready for ope ready + operation
22= ready + operation
23 = motor power
24 = torque
25 = field bus
50 = motor current limit active
4.151/4.171
DOx on
Unit:
min: 0
max.:1,000,000
Parameter manual:
p. xy
Transfer status:
2
def.: 0
own value (
to
be entered!
)
Relationship to
parameter:
4,150/4,170
If the set process value exceeds the switch-on limit, the output is set to 1.
Содержание INVEOR MA
Страница 1: ...Operating manual INVEOR Betriebsanleitung_INVEOR_A5 indd 1 28 02 11 10 33...
Страница 91: ...Guidelines Norms and Standards Operating manual INVEOR 91...
Страница 92: ...Guidelines Norms and Standards 92 Operating manual INVEOR...
Страница 93: ...Guidelines Norms and Standards Operating manual INVEOR 93...