14
Mounting on a substrate with bracket, entries under ground level
K
B
A
E
C
F
M
L
E
ุ
ุ
ป
b
- Distance from the wall when passed
to the wire under ground level: see
"Minimum clearances"
A
- Brackets for ground installation
B
- Bottom sheet openings for free
condensate drain: Do not close holes
C
- Foundation belts
E
- Protection against freezing of the
foundation (compacted gravel, e.g.
from 0 to 32/56 mm), layer thickness in
accordance with local requirements and
construction technology rules
F
- Electrical wires connecting the internal
module to the external module and
supplying the electrical wire of the
external module: Lay the wires without
stress
K
- Pavement, terrrace
L
- Soil
M
- Underground plastic pipe DN 125 with lid
and 3 30° tubular fittings, sealing the duct
passage in the cover within the scope of
the investor's duties
[
[
A
C
D
B
A
- Bracket for mounting on the ground
B
- Gravel substrate for easy condensation
C
- C o n c re t e f o u n d a t i o n : c h a p t e r
"Foundations"
D
- Underground plastic pipe DN 125 (only
for entries under ground level)
Note
We recommend letting condensate drain away
freely (without condensate pipe).