41
EN-114B_f.1294
Indoor module: Terminal strips (signaling and safety connections)
Clamps
Function
Description
X3.1
Switched phase
Via the regulator's power switch
Note
Pay attention to the total load 1000 W
all connected components.
X3.6
X3.7
Power supply blocked by ZE
(factory fitted bridge)
Potential-free contact required turn:
■
Closed: The heat pump is running
■
Open: the heat pump is not
running
■
Connection parameters 230 V ~,
0.15 A.
When connecting, remove the bridge.
Note
■ Parameter setting is not neces-
sarily
■ The compressor is switched off
"permanently", as soon as the
contact is opened.
■ Power failure signal via ZE causes
disconnection supply voltage from
a given component, if applicable
from ZE.
■ For an instantaneous water heat-
er can be selected disabled levels
(parameter “Power for instantane-
ous water heater at the block. ZE
790A ").
■ Control unit electrical connection
heat pumps (3 x 1.5 mm
2
) and
delivery lock signal wire power
via ZE can be connected to 5-wire
cable.
X3.8
X3.9
Only for heat pumps with func
-
tion cooling:
■
Frost protection sensor and /
or Switch humidity 230 V ~
■
Or bridge
For heat pumps without cooling
function:
■
Bridge
Potential-free contact required turn:
■
Closed: the security chain uninter
-
rupted
■
Open: security chain interrupted,
the heat pump is not running
■
Connection parameters 230V~,
0.15 A.