20
Cords length
■
Max. height difference indoor module - outdoor module: 10 m
■
Min. cord length: 5 m
■
Max. cord length:
Types HPS.Z-06/230; HPS.Z-08/230: 25 m
HPS.Z-12/400 types; HPS.Z-16/400: 30 m
Sound and vibration damping
Notes on wiring installation
Wall culvert:
■
No wall opening in load-bearing elements, lintels, elements insulation (e.g. vapor
barriers) etc.
■
Avoid acoustic bridges, ie. contact between the metal (refrigerant line) and the building
structure.
Laying cords:
■
Route the electric lines stress-free and separate from the refrigerant lines.
■
Lay the hot gas line with a bend.
As a result, the transmission of vibrations via the pipe walls is reduced.
The pipe bend can be installed inside or outside the building.
■
Pipe bend to compensate for vibrations with a short hot gas line it should be narrower
than with a longer hot gas line.
■
Insulate all refrigerant pipes.
Fixing the refrigerant lines:
■
Only secure the refrigerant lines with pipe clamps with flexible insulating insert
(EPDM).
■
Attach the vibration compensation pipe bend directly behind the pipe bend (towards
the outer wall).
■
Secure the refrigerant lines with pipe clamps at a distance 2,0 m. We recommend
using clamps to secure the refrigerant lines pipes at a distance of 1,5 m.
■
We recommend the installation of pipe clamps only on components with a weight
per square meter ≥ 250 kg / m
2
.
■
Do not install refrigerant lines on partition walls or ceilings that separate from the
rooms that require a low ceiling noise level (e.g. bedroom).