TP-5867 11/02
18
Section 3 Troubleshooting
General Troubleshooting Chart, continued
Problem
Possible Cause
Corrective Action
Reference
Generator set
starts but
shuts down
Low oil pressure (LOP) shutdown
Correct cause of shutdown.
Check oil level, oil pump, etc.
Sections 4, Controller
Troubleshooting, 6.8, Fault
Shutdown Test Procedure, and
Engine S/M
No generator output voltage
Check AC voltage. Separately
excite unit. Check stator
continuity.
Sections 6, Component Testing
and Adjustments, and 9, Wiring
Diagrams
Voltage regulator fuse blown
Replace fuse.
Section 4, Controller
Troubleshooting
Generator set
starts hard
Air cleaner clogged
Replace element.
Section 2.4, Air Cleaner Element
and Precleaner
Fuel mixture adjustment incorrect
Adjust fuel valve.
Section 6.11, Fuel Systems
Faulty spark plug(s)
Replace and regap spark plug(s).
Section 2.3, Spark Plugs
Defective ignition components
(spark control or ignition module)
Test/replace ignition components.
Engine S/M
Worn piston rings, valves
Check compression.
Engine S/M
Insufficient fuel pressure
Check fuel pressure
Section 6.11.3, Fuel Regulators
Defective spark plug(s)
Replace spark plugs.
Engine O/M
Defective spark plug wire(s)
Replace spark plug wires.
Engine S/M
Generator set
No fuel
Turn on fuel supply.
—
stops
suddenly
Fuel line restriction
Inspect fuel lines.
—
suddenly
Fuel lines too long
Check fuel line length.
Section 6.11.1, Gas Piping
Air cleaner clogged
Replace element.
Section 2.4, Air Cleaner Element
and Precleaner
Fuse blown in controller
Replace fuse.
O/M
Faulty spark plug(s)
Replace and regap plug(s).
Engine S/M
Engine overheated (hot engine
only)
Check air intake, fuel adjustment,
oil level, air inlet/outlet.
Sections 2.5, Cooling System,
2.2, Lubrication System, and 6.11,
Fuel Systems
Overspeed shutdown
Check electronic governor and
voltage regulator.
Section 6.9, Electronic Governor
Low oil pressure (LOP) shutdown
Check engine oil level, oil
pressure, and oil pump.
Sections 2.2.1, Low Oil Pressure
Shutdown, 4.2.4, Low Oil
Pressure (LOP) Shutdown, 6.8,
Fault Shutdown Test Procedure,
and Engine S/M
Defective low oil pressure (LOP)
shutdown switch
Attempt startup. If unit shuts
down, remove lead from LOP
switch and reset controller. A
successful restart attempt
indicates a faulty LOP shutdown
switch.
Note:
Verify engine oil pressure
before performing test and/or
replacing LOP shutdown switch.
Sections 2.2.1, Low Oil Pressure
Shutdown, and 4.2.4, Low Oil
Pressure (LOP) Shutdown
Defective fuel valve/fuel regulator
Check regulator/valve operation.
Sections 2, Scheduled
Maintenance, and 6, Component
Testing and Adjustments
Blown voltage regulator fuse
Replace fuse. If fuse blows again,
test generator components.
Section 6.3, Voltage Regulator
Engine overloaded
Reduce electrical load.
O/M
Overcrank shutdown
Check rotor.
Section 6.4, Main Field (Rotor)
Содержание 11RMY
Страница 1: ...Industrial Generator Sets Models 8 5RMY 11RMY Controllers Relay TP 5867 11 02d Service...
Страница 16: ...TP 5867 11 02 6 Section 1 Specifications Notes...
Страница 32: ...TP 5867 11 02 22 Section 3 Troubleshooting Notes...
Страница 40: ...TP 5867 11 02 30 Section 4 Controller Troubleshooting Notes...
Страница 44: ...TP 5867 11 02 34 Section 5 Generator Relay Controller Troubleshooting Notes...
Страница 68: ...TP 5867 11 02 58 Section 6 Component Testing and Adjustment Notes...
Страница 72: ...TP 5867 11 02 62 Section 7 Generator Reconnection Notes...
Страница 80: ...TP 5867 11 02 70 Section 8 Disassembly Reassembly Notes...
Страница 82: ...TP 5867 11 02 72 Section 9 Wiring Diagrams Notes...
Страница 83: ...TP 5867 11 02 73 Section 9 Diagrams and Drawings Relay Controller Schematic Diagram 1 Phase ADV 6297 B...
Страница 85: ...TP 5867 11 02 75 Section 9 Diagrams and Drawings Relay Controller Schematic Diagram 1 Phase ADV 6297 E...
Страница 87: ...TP 5867 11 02 77 Section 9 Diagrams and Drawings Relay Controller Schematic Diagram ADV 6524...
Страница 88: ...TP 5867 11 02 78 Section 9 Diagrams and Drawings 6 Relay Controller Point to Point Wiring Diagram GM10619...
Страница 96: ......
Страница 97: ......