Section 1 Specifications
Section 1 Specifications
1.1 Introduction
The spec sheets for each generator set provide specific
generator and engine information.
Refer to the
respective spec sheet for data not supplied in this
manual. Consult the generator set installation manual,
engine operation manual, and engine service manual
for additional specifications.
1.2 Controller Features
The generator set is equipped with a relay controller.
For a specific description of the controller, see
Section 2,
Operation,
in
the
operation
manual.
Controller features include the following:
D
Fault shutdowns:
D
Overcrank
D
Overspeed
D
Pressure, low oil
D
High engine temperature
D
Running time meter
D
Switches and standard features:
D
Master switch, RUN/RESET-OFF/AUTO
D
Cranking, cyclic
D
Line circuit breaker
D
Common fault lamp (on some controllers)
1.3 Alternator
The generator is equipped with Kohler’s PowerBoost
t
voltage regulation system, which provides instant
response to load changes.
PowerBoost
t
is a unique system that ensures reliable
motor starting and consistent voltage levels.
PowerBoost
t
utilizes a voltage monitoring system that
employs a winding independent of the field to monitor
and stabilize voltage.
See Figure 1-1 for alternator specifications.
Alternator Specification
8.5/11RMY
Frequency Hz
50/60
Phase
Single-Phase
Number of leads
4
Excitation method
Static Excited
Voltage regulator type
PowerBoost
t
IIIE
Coupling type
Direct
Thrubolt torque, Nm ( ft. lb.)
38 (28)
Overbolt torque, Nm (in. lb.)
7 (60)
Insulation (rotor and stator)
Epoxy varnish, vacuum
impregnated
Units built before 7/1/02
Class 155
Units built after 7/1/02
Class 180
Winding material
Copper
Bearing, number and type
1, replaceable ball
Circuit protection
Controller
10 amps
Voltage regulator
10 amps
Generator AC output
Dependent on voltage
configuration
Rotor resistance, ohms, cold
4.0
Stator resistance, ohms,* cold
Leads: 1-2, 3-4
0.07
33-44
0.07
55-33
0.70
Stator output voltage with
separately excited rotor using
12-volt battery, minimum
Leads: 1-2, 3-4
132V
33-44
132V
55-33
145V
Rotor field voltage/current
readings at rated output
voltage, hot
No load
8V/2.5 amps
Full load
47V/7.4 amps
Brush length, new
19.05 mm (0.75 in.)
* Most ohmmeters do not give accurate readings when
measuring less than 1 ohm. The stator can be considered
good if a low resistance reading (continuity) is obtained and
there is no evidence of shorted windings (discoloration). Do
not confuse a low resistance reading with a reading indicating a
shorted winding.
Figure 1-1
Alternator Specifications
Содержание 11RMY
Страница 1: ...Industrial Generator Sets Models 8 5RMY 11RMY Controllers Relay TP 5867 11 02d Service...
Страница 16: ...TP 5867 11 02 6 Section 1 Specifications Notes...
Страница 32: ...TP 5867 11 02 22 Section 3 Troubleshooting Notes...
Страница 40: ...TP 5867 11 02 30 Section 4 Controller Troubleshooting Notes...
Страница 44: ...TP 5867 11 02 34 Section 5 Generator Relay Controller Troubleshooting Notes...
Страница 68: ...TP 5867 11 02 58 Section 6 Component Testing and Adjustment Notes...
Страница 72: ...TP 5867 11 02 62 Section 7 Generator Reconnection Notes...
Страница 80: ...TP 5867 11 02 70 Section 8 Disassembly Reassembly Notes...
Страница 82: ...TP 5867 11 02 72 Section 9 Wiring Diagrams Notes...
Страница 83: ...TP 5867 11 02 73 Section 9 Diagrams and Drawings Relay Controller Schematic Diagram 1 Phase ADV 6297 B...
Страница 85: ...TP 5867 11 02 75 Section 9 Diagrams and Drawings Relay Controller Schematic Diagram 1 Phase ADV 6297 E...
Страница 87: ...TP 5867 11 02 77 Section 9 Diagrams and Drawings Relay Controller Schematic Diagram ADV 6524...
Страница 88: ...TP 5867 11 02 78 Section 9 Diagrams and Drawings 6 Relay Controller Point to Point Wiring Diagram GM10619...
Страница 96: ......
Страница 97: ......