21
Section 3 Troubleshooting
Problem
Possible Cause
Corrective Action
Reference
No generator
output voltage
Defective stator (open, grounded, or
shorted windings)
Test and/or replace.
Section 6, Component
Testing and Adjustment
p
g
K1 relay (NC) contact open
Check continuity.
Section 4, Controller
Troubleshooting and 9,
Wiring Diagrams
Brushes sticking in holder
Check springs and alignment.
Section 6.6, Brushes
Rotor slip rings dirty or corroded
Check and/or service.
Section 6.6, Brushes
Worn brushes
Replace worn brushes.
Section 6.6, Brushes
Defective or misadjusted voltage
regulator
Excite (rotor) separately.
Section 6, Separate
Excitation, and 6.3.1, Voltage
Regulator Test
Low engine rpm
Check engine speed using a
tachometer or frequency meter.
Note:
Hz x 60 = rpm
(Example 57 x 60 = 3420 rpm)
—
No AC output
Circuit breaker open or defective, if
equipped
Reset breaker to ON position.
Check AC voltage on generator
side of circuit breaker.
Section 1.6, Service Views,
for location
Circuit breaker tripping because of
overload on generator set
Reduce load.
O/M
No battery voltage to voltage regulator
during cranking: (+) and (--) terminals
on regulator
Check for DC voltage at voltage
regulator terminals listed.
Sections 6.3, Voltage
Regulator, and 9, Wiring
Diagrams
Blown voltage regulator fuse
Replace fuse; if fuse blows again,
check voltage regulator and/or
stator auxiliary windings.
Sections 6.3, Voltage
Regulator, and 9, Wiring
Diagrams
Open wiring, terminal, or pin in buildup
circuit or voltage regulator circuit
Check continuity.
Sections 6.3, Voltage
Regulator, and 9, Wiring
Diagrams
Brushes sticking in brush holder or
broken brush spring
Check brush position and
condition.
Section 6.6, Brushes
Rotor slip rings dirty or corroded
Check slip ring condition.
Section 6.4, Main Field
(Rotor)
Defective rotor (grounded windings)
Check voltage and continuity.
Section 6.4, Main Field
(Rotor)
Defective stator (open, grounded, or
shorted windings)
Check voltage and continuity.
Section 6.5, Stator
Defective or misadjusted voltage
regulator
Excite rotor separately and check
for AC output. Readjust voltage
regulator.
Section 6.3, Voltage
Regulator
Defective K3 relay (field flashing) in
relay controller circuit board
Test/replace relay controller circuit
board.
Section 4, Controller
Troubleshooting
Содержание 11RMY
Страница 1: ...Industrial Generator Sets Models 8 5RMY 11RMY Controllers Relay TP 5867 11 02d Service...
Страница 16: ...TP 5867 11 02 6 Section 1 Specifications Notes...
Страница 32: ...TP 5867 11 02 22 Section 3 Troubleshooting Notes...
Страница 40: ...TP 5867 11 02 30 Section 4 Controller Troubleshooting Notes...
Страница 44: ...TP 5867 11 02 34 Section 5 Generator Relay Controller Troubleshooting Notes...
Страница 68: ...TP 5867 11 02 58 Section 6 Component Testing and Adjustment Notes...
Страница 72: ...TP 5867 11 02 62 Section 7 Generator Reconnection Notes...
Страница 80: ...TP 5867 11 02 70 Section 8 Disassembly Reassembly Notes...
Страница 82: ...TP 5867 11 02 72 Section 9 Wiring Diagrams Notes...
Страница 83: ...TP 5867 11 02 73 Section 9 Diagrams and Drawings Relay Controller Schematic Diagram 1 Phase ADV 6297 B...
Страница 85: ...TP 5867 11 02 75 Section 9 Diagrams and Drawings Relay Controller Schematic Diagram 1 Phase ADV 6297 E...
Страница 87: ...TP 5867 11 02 77 Section 9 Diagrams and Drawings Relay Controller Schematic Diagram ADV 6524...
Страница 88: ...TP 5867 11 02 78 Section 9 Diagrams and Drawings 6 Relay Controller Point to Point Wiring Diagram GM10619...
Страница 96: ......
Страница 97: ......