TP-5867 11/02
17
Section 3 Troubleshooting
Section 3 Troubleshooting
Use the following tables as a quick reference in
troubleshooting individual problems.
Generator set
faults are listed in groups and include likely causes and
remedies. The reference column provides additional
sources of information in this and related manuals
regarding the problem and solution. Corrective action
and testing in many cases requires knowledge of
electrical and electronic circuits. Have an authorized
service distributor/dealer perform service work.
General Troubleshooting Chart
Problem
Possible Cause
Corrective Action
Reference
Generator set
d
k
Weak or dead battery
Recharge or replace battery.
Operation Manual (O/M)
does not crank
Reversed or poor battery
connections
Check connections.
—
Defective starter relay
Check continuity of circuit.
Sections 6, Component Testing
and Adjustment, and 9, Wiring
Diagrams
Defective starter
Rebuild or replace.
Engine Service Manual (S/M)
Defective controller start/stop
switch
Test function of switch.
Sections 4, Controller
Troubleshooting and 9, Wiring
Diagrams
Fuse blown in controller
Replace fuse; if fuse blows again,
check circuit and components.
Section 4, Controller
Troubleshooting, and O/M
Open circuit in wiring, terminals
pin, circuit board, etc.
Check continuity.
Sections 4, Controller
Troubleshooting and 9, Wiring
Diagrams
Defective controller circuit board
Check circuit board operation.
Section 4, Controller
Troubleshooting
Overcrank shutdown
Check engine fuel and ignition
systems. Shutdown occurs after
30 seconds of cyclic cranking.
Section 6.11, Fuel Systems, and
Engine S/M for ignition system
information
Faulty spark plugs or loose
connections
Replace and regap spark plugs.
Section 2.3, Spark Plugs
Defective fuel regulator/valve
Check regulator/valve operation.
Sections 6.11, Fuel Systems, and
4, Controller Troubleshooting
Faulty ground (--) connection
Clean and retighten.
—
Insufficient fuel pressure on
LP/natural gas systems
Check fuel pressure
Section 6.11.3, Fuel Regulators
Weak or dead battery
Recharge or replace.
Section 2.7, Battery
Generator set
k b
Fuel not turned on
Turn on fuel valve.
—
cranks but
does not start
Air cleaner clogged
Clean or replace.
Section 2.4, Air Cleaner Element
and Precleaner
Defective ignition system spark
control or ignition coil
Test and/or replace components.
Engine S/M
Blown voltage regulator fuse
Replace fuse. If fuse blows again,
check generator components.
O/M
Blown controller fuse
Replace fuse; if fuse blows again,
check circuit and components.
Section 4, Controller
Troubleshooting, and O/M
Open wiring terminal or pin
(P2 connector)
Check continuity.
Section 9, Wiring Diagrams
Overspeed setting on electronic
governor board set too low
Readjust overspeed on governor
board.
—
Содержание 11RMY
Страница 1: ...Industrial Generator Sets Models 8 5RMY 11RMY Controllers Relay TP 5867 11 02d Service...
Страница 16: ...TP 5867 11 02 6 Section 1 Specifications Notes...
Страница 32: ...TP 5867 11 02 22 Section 3 Troubleshooting Notes...
Страница 40: ...TP 5867 11 02 30 Section 4 Controller Troubleshooting Notes...
Страница 44: ...TP 5867 11 02 34 Section 5 Generator Relay Controller Troubleshooting Notes...
Страница 68: ...TP 5867 11 02 58 Section 6 Component Testing and Adjustment Notes...
Страница 72: ...TP 5867 11 02 62 Section 7 Generator Reconnection Notes...
Страница 80: ...TP 5867 11 02 70 Section 8 Disassembly Reassembly Notes...
Страница 82: ...TP 5867 11 02 72 Section 9 Wiring Diagrams Notes...
Страница 83: ...TP 5867 11 02 73 Section 9 Diagrams and Drawings Relay Controller Schematic Diagram 1 Phase ADV 6297 B...
Страница 85: ...TP 5867 11 02 75 Section 9 Diagrams and Drawings Relay Controller Schematic Diagram 1 Phase ADV 6297 E...
Страница 87: ...TP 5867 11 02 77 Section 9 Diagrams and Drawings Relay Controller Schematic Diagram ADV 6524...
Страница 88: ...TP 5867 11 02 78 Section 9 Diagrams and Drawings 6 Relay Controller Point to Point Wiring Diagram GM10619...
Страница 96: ......
Страница 97: ......