TP-5867 11/02
44
Section 6 Component Testing and Adjustment
Component
Ohmmeter
Connections
Ohmmeter
Scale
Generator Set
Master Switch
Position
Ohmmeter Readings for Operative
Components*
Generator set master
switch
P1-2 (47) and P1-14 (N)
R x 1000
RUN
Zero ohms (continuity). Any other reading
indicates a defective switch.
switch
OFF/RESET
No reading (open circuit). Any other
reading indicates a defective switch.
Hourmeter
(+) and (--) terminals
R x 1
OFF/RESET
Continuity (low resistance). If no
continuity is found, replace the hourmeter.
P1 wiring harness
P1-14 and ground
R x 1
OFF/RESET
Zero ohms (continuity)
Any other reading indicates a poor ground
connection.
P1-12 and P1-15 (stator
leads 1 & 2, 1 phase)
R x 1
OFF/RESET
Zero ohms (continuity).
Controller 10-amp fuse and
wiring
P1-10 and battery positive
(+) cable
R x 100
OFF/RESET
Zero ohms (continuity). If no continuity is
found, check for an open circuit and/or a
blown fuse.
Voltage regulator circuit
10 amp fuse
P10-5 and stator lead 55 at
the fuse holder (relay
controller)
R x 100
OFF/RESET
Zero ohms (continuity). If no continuity is
found, check for an open circuit and/or a
blown fuse.
Low oil pressure switch*
Lead 13 and ground
(engine block)
R x 1000
OFF/RESET
Zero ohms (continuity). No continuity
indicates a defective switch and/or wiring.
High engine temperature
switch
Lead 37 and ground
(engine block)
R x 1000
OFF/RESET
No reading (open circuit). Any other
reading indicates a defective switch.
Starter relay
(See illustration below)
Starter relay terminal and
relay base (ground)
R x 1
OFF/RESET
5--6 ohms. Lower resistance indicates a
shorted relay coil and/or wiring. High
resistance indicates an open relay coil
and/or wiring.
Cyclic crank relay and
wiring
C
7
8
5
6
3
4
1
2
Disconnect the relay and
remove it from the
controller. Connect the
ohmmeter to relay
terminals 7 and 8.
R x 1
—
160 ohms
* See Section 6.8, Fault Shutdown Test Procedure
Figure 6-15
Continuity Checks
Содержание 11RMY
Страница 1: ...Industrial Generator Sets Models 8 5RMY 11RMY Controllers Relay TP 5867 11 02d Service...
Страница 16: ...TP 5867 11 02 6 Section 1 Specifications Notes...
Страница 32: ...TP 5867 11 02 22 Section 3 Troubleshooting Notes...
Страница 40: ...TP 5867 11 02 30 Section 4 Controller Troubleshooting Notes...
Страница 44: ...TP 5867 11 02 34 Section 5 Generator Relay Controller Troubleshooting Notes...
Страница 68: ...TP 5867 11 02 58 Section 6 Component Testing and Adjustment Notes...
Страница 72: ...TP 5867 11 02 62 Section 7 Generator Reconnection Notes...
Страница 80: ...TP 5867 11 02 70 Section 8 Disassembly Reassembly Notes...
Страница 82: ...TP 5867 11 02 72 Section 9 Wiring Diagrams Notes...
Страница 83: ...TP 5867 11 02 73 Section 9 Diagrams and Drawings Relay Controller Schematic Diagram 1 Phase ADV 6297 B...
Страница 85: ...TP 5867 11 02 75 Section 9 Diagrams and Drawings Relay Controller Schematic Diagram 1 Phase ADV 6297 E...
Страница 87: ...TP 5867 11 02 77 Section 9 Diagrams and Drawings Relay Controller Schematic Diagram ADV 6524...
Страница 88: ...TP 5867 11 02 78 Section 9 Diagrams and Drawings 6 Relay Controller Point to Point Wiring Diagram GM10619...
Страница 96: ......
Страница 97: ......