- 10 -

Setup Guidelines

● Setting parameters

While the basic screen is displayed, hold down the 

 key 

for about two seconds to enter the function select mode. Next, 

hold down the 

 key again for about two seconds to enter 

parameter setting mode. 

Example of display when 

setting parameter items 

Example of display 

during setting 

Use the   and   keys to scroll through the setting items 

and display the one you want. Next, press the 

 

key. 

This will display a value with the rightmost digit flashing. 

Press the 

 key to move the flashing to the left. 

 flashing 

 flashing 

key 

Use the   and   keys to change the value of the currently flashing 

digit. Use the   and   keys to change each of the digits until the 

value is the one you want. 

After the value is the one you want, press the 

 key. 

This will display the setting item and its set value.

To configure other settings, repeat steps 

 through 

 as many time 

as required. 

To exit the setting procedure, while a setting item is displayed 

hold down the 

 key for about two seconds to return to 

the basic screen. 

Function settings mode 

Display item selection 

・・・

key 2 seconds

Basic screen

key 2 seconds

key 2 seconds

Basic screen

Setting parameters mode 

key 

key 

key 

key 

key 

key 

Settings

 Note

・・・

key 

key 

key 

key 

key 

key 

key 

key 

key 

key 

key 

key 

・・

・・

・・

Note: As the setting values increase, 9 becomes 0 

and the value to the left increases by 1. In 
the same way, as the value decreases 0 
becomes 9 and the value to the left 
decreases by 1. 

key 

key 

Function setting list

Function 

number Description

Setting number and 

description

De-

fault

Remarks

Setting key 

lock

00: No key lock

01: Key lock

00

You can also use this setting 

to cancel key lock. 

Performing a change 

operation while key lock is 

engaged will cause "

to be displayed. 

Display unit 

setting

Instantaneous flow rate, 

integrated flow rate

Note

00:

/min, 

01: m

3

/h, m

3

02: m

3

/min, m

3

03: kg/h, kg

00

Caution: After changing the 

unit, existing integrated 

values continue to be 

integrated in the previous 

unit. They are not converted 

automatically. After changing 

the unit, reset integration 

before using it again. 

 The peak value and lower 

value are reset when the 

unit is changed. 

Switch output

00: Not used

01: Instantaneous flow rate upper limit

02: Instantaneous flow rate lower limit

03: Instantaneous flow rate range

04: Instantaneous flow rate upper limit 

(inverted)

05: Instantaneous flow rate lower limit 

(inverted)

06: Instantaneous flow rate range 

(inverted)

07: Integrated count up

08: Integrated count up (inverted)

09: Integrated countdown

10: Integrated count down (inverted)

11: Integrated pulse (minimum unit)

12: Integrated pulse

 

  (Minimum unit x 10)

13: Integrated pulse

 

  (Minimum unit x 100)

14: Alarm generation switch

15: Alarm generation switch (inverted)

00 Inversion causes output ON 

and OFF to be inverted. 

Basic screen

00: Instantaneous flow rate 

screen

01: Integrated lowest digit screen

02: Integrated highest digit 

screen

00

Determines the content of the 

flow rate display when power 

is turned on. 

The function setting mode is 

entered from the basic screen. 

Switch wait 00: Not used

01: Use

00

Gas type

00: Air, nitrogen (fixed)

00 Cannot be changed. 

Operating 

pressure

00: 0. 3 MPa standard

01: 0. 1 MPa standard

02: 0. 5 MPa standard

03: 0. 7 MPa standard

00

When the installation attitude 

is "Installation attitude 2" or 

"Installation attitude 3", error 

due to installation attitude 

can be reduced by 

maintenance mode pressure 

compensation adjustment 

value and operating 

pressure. 

For details, see "●Mainte-

nance Mode" on page 13. 

Reference value 

conversion

00 to 35℃ (1℃ steps)

00 Changing setting resets peak 

value and lower value. 

Integration 

options

00: Integration with only normal flow rate

01: Integration with back flow compensation 00

Integrated 

pulse width

00: 50 ms

01: 250 ms

02: 500 ms

00

Fixed output 

during alarm

00: Not used

01: Up

02: Down (fixed)

00

Outputs a fixed value from 

instantaneous flow rate 

output when a sensor 

abnormality or memory 

abnormality occurs. Flow 

rate indication is zero when 

an alarm occurs. 

Note:  After changing the display unit setting, select the provided 

sticker that corresponds to the new unit and affix it to the flow 

meter. 

Содержание FA Series

Страница 1: ...FA Series Flow Meter 注 bタイプの使用サイズは左右 50mm 120mm未満 このデータからの縮率は 50 120 未満 M140787 Ver 3 0 Instruction Manual Ver 3 0 Details ...

Страница 2: ...pecifications 16 Order Codes 17 Pressure Loss 18 Dimensions 19 Thank you for purchasing a Koganei FA Series Flow Meter To ensure safe use of this product be sure to read the contents of this manual and gain an understanding of how to properly operate the product before actually trying to use it Keep this manual in a safe place for future reference Contents ...

Страница 3: ...ing work etc to mechanisms attached to the product while the product is operating Abnormal operation creates the risk of personal injury WARNING Do not use the product in excess of its specification range Doing so creates the risk of product breakdown loss of function or damage It could also drastically reduce the product s operating life Before supplying air or electricity to the device and befor...

Страница 4: ...anei parts or compatible parts recommended parts Always observe the prescribed methods and procedures 2 Never attempt inappropriate disassembly or assembly of the product relating to basic configurations or its performance or functions Koganei shall not be held responsible for any problems that occur as a result of these items not being properly observed General Precautions Mounting location Avoid...

Страница 5: ...g piping apply an appropriate amount of sealant Do not apply sealant to the first two threads of the end of the pipe Over application of sealant can cause it to get inside the piping creating the risk of measurement error and damage to the FA Series Flow Meter 7 If different diameter piping a regulator filter valve or other piping equipment is installed upstream from the FA Series Flow Meter be su...

Страница 6: ...straight pipe is straight piping that is the same bore diameter as the flow meter The following types of pipes are suitable as straight pipe carbon steel pipes for ordinary piping JIS G3452 carbon steel pipes for pressure service JIS G3454 Schedule 40 or less and stainless steel pipes JIS G3459 Schedule 40 Note 1 For equipment not included in the table below provide 15D or larger straight piping w...

Страница 7: ...ctor separately from power lines and high voltage lines use a separate conduit Noise from these lines may cause the equipment to operate erratically 3 When connecting a cable with connector align the core wire and push it in as far as it will go Next tighten the connector nut by hand When tightening the nut be sure to keep it within the prescribed torque 0 4 to 0 6N m range Failure to do so create...

Страница 8: ...grated value reaches 0 The integrated value is saved to non volatile memory at 10 minute intervals Note that this means depending on the power off timing the latest maximum 10 minute interval integrated value may not have been recorded Also note that there is no recording for an integrated countdown To reset the integrated value hold down the and keys at the same time for at least five seconds whi...

Страница 9: ...s flow rate switch 1 parameter is exceeded Instantaneous flow rate lower limit switch Outputs when the value set with the instantaneous flow rate switch 1 parameter is subceeded Instantaneous flow rate range switch Outputs when instantaneous flow rate is within the range set by instantaneous flow rate switch 1 and instantaneous flow rate switch 2 Integrated flow rate count up switch Outputs when t...

Страница 10: ...eys by pressing with a mechanical pencil a screw driver or any other pointed object Doing so can lead to malfunction CAUTION Function settings While the basic screen is displayed hold down the key for about two seconds The three digits on the left will show the function number while the two digits on the right will show the current setting of the function Example of display Function number Current...

Страница 11: ...ious unit They are not converted automatically After changing the unit reset integration before using it again The peak value and lower value are reset when the unit is changed Switch output 00 Not used 01 Instantaneous flow rate upper limit 02 Instantaneous flow rate lower limit 03 Instantaneous flow rate range 04 Instantaneous flow rate upper limit inverted 05 Instantaneous flow rate lower limit...

Страница 12: ...t cannot be obtained when the setting values is less than 10 of FS Setting zero outputs fixed output during an alarm Reconfigure this setting after changing the display unit setting with function selection Analog output 4mAflow rate specificationNote 1 Flowratevalue equivalentto0to400 FScanbeset Note5 0 Settings are values with decimal points removed Decimal points will be added with model setting...

Страница 13: ... flow rate screen is displayed hold down the key for about two seconds This will change to the instantaneous flow rate lower value screen which alternate between and the lower value To exit the lower value screen press the key This will return to the instantaneous flow rate screen or integrated flow rate screen To clear the current instantaneous flow rate lower value display the lower value and th...

Страница 14: ...ure compensation Channel ID number 0 Adjustment value Configured when using the replacement bypass unit Settings register main channel characteristic values Not displayed for FAS 002 FAS 005 Do not change except when replacing bypass unit Cannot be changed without inputting a password for the reservation code Channel ID number 1 Adjustment value Channel ID number 2 Adjustment value Model FAS 030 2...

Страница 15: ...ck flow The alarm will cease displaying when the actual flow rate becomes within the display range flow rate Registration data abnormal ity 1 Abnormal channel ID numbers registered Correct flow rate calculation cannot be performed The registered channel ID numbers may be wrong Use maintenance mode to register the correct channel ID numbers Note 2 If changing the setting does not clear the alarm tu...

Страница 16: ...mber label of the main channel ー ー Body Number Channel ID number 0 Channel ID number 1 Channel ID number 2 Model numbers are 2 for the FAS 030 3 for the FAS 060 and 4 for the FAS 120 Be sure to double check the channel ID numbers and the model number after you input them 4 Check to make sure that the instantaneous flow rate display shows zero 5 Apply pressure to the flow meter and inside the pipin...

Страница 17: ...01 MPa 1 digit 5 to 100 of FS flow 1 current output 4 to 20 mA Output range 3 2 to 20 8 mA Fixed output during alarm up 21 6 0 4 mA initial default modifiable by setting Fixed output during alarm down 0 0 0 4 mA fixed Allowable load resistance 300 Ωmax Maximum output current 24 mA max Within 1 5 s For 0 100 FS step input time to reach 95 of maximum value Calculation cycle 50 ms Rc 1 4 Rc 1 2 Rc1 R...

Страница 18: ...channel material Bypass unit Gasket Bypass unit case material Load mass kg Semiconductor non volatile memory EEPROM Recorded data Function settings parameters integrated values etc 50 MΩ min Between connector pin and main channel or mounting bolts by 500VDC megger Option with connector oil resistant flame retardant cable UL2464 EN standard See Installation attitudes on page 4 IP65 JISC0920 and IEC...

Страница 19: ...5 0 1 MPa Primary side pressure 0 7 MPa 0 3 MPa 0 5 MPa 0 1000 6000 5000 4000 0 2000 3000 Flow rate R min normal 0 1 MPa Primary side pressure 0 7 MPa 0 3 MPa 0 5 MPa 0 80 20 40 60 Pressure loss kPa Pressure loss kPa FAS 060 20 5 10 15 0 1 MPa Primary side pressure 0 7 MPa 0 3 MPa 0 5 MPa 0 1000 6000 5000 4000 0 2000 3000 Flow rate R min normal 0 1 MPa Primary side pressure 0 7 MPa 0 3 MPa 0 5 MPa...

Страница 20: ...threaded mounting hole 2 M4 x 0 7 depth 7 87 8 90 78 75 63 4 5 5 5 Mounting bracket B FAS 030 FAS 002 2 Rc1 4 FAS 005 2 Rc1 2 threaded mounting hole 2 M4 x 0 7 depth 7 46 5 15 34 75 47 13 5 24 48 27 65 8 1 5 73 8 23 5 IN OUT φ6 90 78 75 63 4 5 5 5 Mounting bracket B M12 connector Cable with connector option 2NL Cable length 2000 mm 5NL Cable length 5000 mm FAS 002 FAS 005 ...

Страница 21: ...th 2000 mm 5NL Cable length 5000 mm φ6 M12 connector threaded mounting hole 2 M5 x 0 8 depth 7 IN OUT FAS 060 2 Rc2 34 17 61 30 5 110 106 8 75 37 5 75 87 5 37 5 Cable with connector option 2NL Cable length 2000 mm 5NL Cable length 5000 mm φ6 M12 connector threaded mounting hole 2 M5 x 0 8 depth 7 OUT IN FAS 120 ...

Страница 22: ...φ4 5 Cross head pan screw M4 0 7 length 6 2 pcs supplied 48 78 90 Additional Parts Dimensions mm φ6 φ14 40 40 FAK 2L 2000 FAK 5L 5000 Bypass unit FAB Mounting bracket B FAS Cable with connector option FAK 2L Cable length 2000 mm Yamatake Corporation FAK 5L Cable length 5000 mm ...

Страница 23: ...tact the Overseas Department below Inquiries Koganei Corporation Overseas Department 3 11 28 Midori cho Koganei City Tokyo 184 8533 TEL 042 383 7172 FAX 042 383 7206 Revision History Ver 2 0 P17 The order codes of Lenght of cable with connector will be changed as bellow 2L 2NL 5L 5NL The order code of cable with connector in additional parts will be changed as below PA5 41S 2MK E FAK 2L PA5 41S 5M...

Страница 24: ...hina Tel 021 6145 7313 Fax 021 6145 7323 KOGANEI PORNCHAI CO LTD 89 174 Moo 3 Vibhavadee Rangsit Road Talad Bangkhen Laksi Bangkok 10210 Thailand Tel 02 551 4025 Fax 02 551 4015 KOGANEI KOREA CO LTD Room 301 Donghwa Bld 25 5 Yoido Yongdeunpo Gu Seoul Korea Tel 02 786 0413 Fax 02 786 0415 For other information and more detailed specifications see the product catalog For inquiries about the product ...

Отзывы: