background image

- 5 -

Handling Instructions and Precautions

 Note  4:Contact Koganei about 1 1/2B and 2B size filters and mist filters. 

 

5:  Straight pipe section required connecting a filter with the same bore diameter as the flow meter. 

 

6:  An example of connecting contraction piping on FAS-002 (product specification range 

of within ±3% FS) is shown below. 

When connecting piping one size larger (such as 1/2B on FAS-002), use a prescribed 

value of +5D for the upstream straight pipe section* and +5D for the downstream 

straight pipe section. 

* Length when piping one size larger than the prescribed value is connected. 

 7: 

 An example of connecting expansion piping on FAS-005 (product specification range 

of within ±3% FS) is shown below. 

Do not connect piping with a diameter smaller than the connection pipe bore diameter 

without straight section piping. Even if flow in the main channel itself is normal direction 

flow, bypass unit back flow can produce a negative reading. Also, the readout may 

show an extremely low flow rate instead of the actual flow rate. 

When connecting piping one size smaller (such as 1/4B on FAS-005), use a prescribed 

value of +10D for the upstream straight pipe section* and +5D for the downstream 

straight pipe section. 

* Length when piping one size smaller than the prescribed value is connected. 

 8: 

 The illustration below shows single-elbow and double-elbow configuration. 

 

9:  Install the flow rate adjustment valve downstream from the flow meter.

  10:  The distance from the flow meter to an elbow should be greater than the prescribed 

length. Piping from the regulator to the flow meter can be either tube piping or bent by 

an elbow. However, when connecting to the flow meter with an elbow be sure to 

provide the straight pipe section required by the elbow. Provide distance when 

installing a filter and mist filter between the flow meter and elbow. 

5D

FAS-002

1/4B

3/8B

3/8B

10D

5D

FAS-002

1/2B

1/4B

1/4B

1/2B

15D

FAS-005

1/2B

3/8B

3/8B

25D

5D

FAS-005

1/2B

1/4B

1/2B

1/4B

10D

Single elbow 

10D

Double elbow 

Elbow

Distance from flow meter 

FAS-002: 200 D or more 

Other equipment: 30 D or more 

Straight pipe 

minimum of 

10 D

Regulator 

Filter

 Whenever there is the risk of foreign matter (dust, sediment, oil mist, etc.) being 

mixed in with the measured fluid, be sure to install upstream from the FA Series Flow 

Meter a filter and mist filter that can remove foreign matter measuring 1μm or larger. 

 Periodically inspect and replace filters, and perform any other necessary filter maintenance. 

Specification accuracy and straight pipe section

Install the FA Series Flow Meter so the arrow marked on its label is pointed in the same 

direction as the fluid flow direction. When connecting different diameter tubing, valves, 

filters, and other equipment, provides straight pipe in accordance with the information in the 

table below. 

A "straight pipe" is straight piping that is the same bore diameter as the flow meter. The 

following types of pipes are suitable as straight pipe: carbon steel pipes for ordinary piping 

(JIS G3452), carbon steel pipes for pressure service (JIS G3454), Schedule 40 or less, and 

stainless steel pipes (JIS G3459), Schedule 40.

Note 1. 

For equipment not included in the table below, provide 15D or larger straight piping when 

installing it upstream from the FA Series Flow Meter, and 5D or larger straight piping when 

installing it downstream from the FA Series Flow Meter. The letter D represents the bore 

diameter.

Note 2. 

When measuring back flow in addition to normal flow, the same length as the upstream 

straight pipe is required downstream from the FA Series Flow Meter. 

Pipe, connected equipment Connection 

location

Straight pipe section for FA Series Flow Meter

Specification 

range

Within (±3%FS)

Accuracy

Within ±5%FS

Mist filter

For FAS-002, FAS-005, FAS-030

Notes 3, 5

Upstream from  

flow meter

10D

Not required

Mist filter

For FAS-060, FAS-120

Notes 4, 5

Upstream from  

flow meter

20D

Not required

1 size larger bore diameter piping

(contraction piping connection)

FAS-002 3/8B

1/4B

FAS-005 3/4B

1/2B

FAS-030  1 1/4B

1B

FAS-060 2B

1 1/2B

Note 6

Upstream from  

flow meter

5D

Not required

Downstream  

from flow meter Not required

Not required

More than 1 size larger bore 

diameter piping

(contraction piping connection)

FAS-120  2 1/2B

2B

Note 6

Upstream from  

flow meter

10D

5D

Downstream 

from flow meter

5D

5D

1 size smaller bore diameter piping

(expansion piping connection)

FAS-002 1/8B

1/4B

FAS-005 3/8B

1/2B

FAS-030 3/4B

1B

FAS-060  1 1/4B

1 1/2B

Note 7

Upstream from  

flow meter

15D

Not required

Downstream  

from flow meter Not required

Not required

More than 1 size smaller bore 

diameter piping

(expansion piping connection)

FAS-120  1 1/2B

2B

Note 7

Upstream from  

flow meter

25D

10D

Downstream  

from flow meter

5D

5D

Single elbow

Note 8

Upstream from flow meter

10D

Not required

Downstream from flow meter Not required

Not required

Double elbow

Note 8

Upstream from flow meter

10D

10D

Downstream from flow meter Not required

Not required

Ball valve

(Full bore type, fully open)

Note 9

Upstream from flow meter

20D

10D

Downstream from flow meter

10D

5D

Regulator

Note 10

FAS-002

Upstream from flow meter

200D

Not required

Downstream from flow meter

10D

Not required

Regulator

Note 10

FAS-005FAS-030FAS-060

FAS-120

Upstream from flow meter

30D

Not required

Downstream from flow meter

5D

Not required

Air filter

Upstream from flow meter

25D

Not required

 Note 1: 

 Note that accuracy deteriorates when piping carbon steel pipes for 

pressure service (JIS G3454) or stainless steel pipes (JIS G3459), 

larger than Schedule 40 is connected. A larger schedule results in a 

smaller pipe inside diameter which causes a pipe effect and 

deteriorated accuracy. 

 

2:  The approximate D (bore diameter) for FAS-002 (1/4B) is 8 mm, for 

FAS-005 (1/2B) is 15 mm, for FAS-030 (1B) is 25 mm, for FAS-060 (1 

1/2B) is 40 mm, and for FAS-120 (2B) is 50 mm.  

 

3:  Always provide a filter upstream from the mist filter. 

Содержание FA Series

Страница 1: ...FA Series Flow Meter 注 bタイプの使用サイズは左右 50mm 120mm未満 このデータからの縮率は 50 120 未満 M140787 Ver 3 0 Instruction Manual Ver 3 0 Details ...

Страница 2: ...pecifications 16 Order Codes 17 Pressure Loss 18 Dimensions 19 Thank you for purchasing a Koganei FA Series Flow Meter To ensure safe use of this product be sure to read the contents of this manual and gain an understanding of how to properly operate the product before actually trying to use it Keep this manual in a safe place for future reference Contents ...

Страница 3: ...ing work etc to mechanisms attached to the product while the product is operating Abnormal operation creates the risk of personal injury WARNING Do not use the product in excess of its specification range Doing so creates the risk of product breakdown loss of function or damage It could also drastically reduce the product s operating life Before supplying air or electricity to the device and befor...

Страница 4: ...anei parts or compatible parts recommended parts Always observe the prescribed methods and procedures 2 Never attempt inappropriate disassembly or assembly of the product relating to basic configurations or its performance or functions Koganei shall not be held responsible for any problems that occur as a result of these items not being properly observed General Precautions Mounting location Avoid...

Страница 5: ...g piping apply an appropriate amount of sealant Do not apply sealant to the first two threads of the end of the pipe Over application of sealant can cause it to get inside the piping creating the risk of measurement error and damage to the FA Series Flow Meter 7 If different diameter piping a regulator filter valve or other piping equipment is installed upstream from the FA Series Flow Meter be su...

Страница 6: ...straight pipe is straight piping that is the same bore diameter as the flow meter The following types of pipes are suitable as straight pipe carbon steel pipes for ordinary piping JIS G3452 carbon steel pipes for pressure service JIS G3454 Schedule 40 or less and stainless steel pipes JIS G3459 Schedule 40 Note 1 For equipment not included in the table below provide 15D or larger straight piping w...

Страница 7: ...ctor separately from power lines and high voltage lines use a separate conduit Noise from these lines may cause the equipment to operate erratically 3 When connecting a cable with connector align the core wire and push it in as far as it will go Next tighten the connector nut by hand When tightening the nut be sure to keep it within the prescribed torque 0 4 to 0 6N m range Failure to do so create...

Страница 8: ...grated value reaches 0 The integrated value is saved to non volatile memory at 10 minute intervals Note that this means depending on the power off timing the latest maximum 10 minute interval integrated value may not have been recorded Also note that there is no recording for an integrated countdown To reset the integrated value hold down the and keys at the same time for at least five seconds whi...

Страница 9: ...s flow rate switch 1 parameter is exceeded Instantaneous flow rate lower limit switch Outputs when the value set with the instantaneous flow rate switch 1 parameter is subceeded Instantaneous flow rate range switch Outputs when instantaneous flow rate is within the range set by instantaneous flow rate switch 1 and instantaneous flow rate switch 2 Integrated flow rate count up switch Outputs when t...

Страница 10: ...eys by pressing with a mechanical pencil a screw driver or any other pointed object Doing so can lead to malfunction CAUTION Function settings While the basic screen is displayed hold down the key for about two seconds The three digits on the left will show the function number while the two digits on the right will show the current setting of the function Example of display Function number Current...

Страница 11: ...ious unit They are not converted automatically After changing the unit reset integration before using it again The peak value and lower value are reset when the unit is changed Switch output 00 Not used 01 Instantaneous flow rate upper limit 02 Instantaneous flow rate lower limit 03 Instantaneous flow rate range 04 Instantaneous flow rate upper limit inverted 05 Instantaneous flow rate lower limit...

Страница 12: ...t cannot be obtained when the setting values is less than 10 of FS Setting zero outputs fixed output during an alarm Reconfigure this setting after changing the display unit setting with function selection Analog output 4mAflow rate specificationNote 1 Flowratevalue equivalentto0to400 FScanbeset Note5 0 Settings are values with decimal points removed Decimal points will be added with model setting...

Страница 13: ... flow rate screen is displayed hold down the key for about two seconds This will change to the instantaneous flow rate lower value screen which alternate between and the lower value To exit the lower value screen press the key This will return to the instantaneous flow rate screen or integrated flow rate screen To clear the current instantaneous flow rate lower value display the lower value and th...

Страница 14: ...ure compensation Channel ID number 0 Adjustment value Configured when using the replacement bypass unit Settings register main channel characteristic values Not displayed for FAS 002 FAS 005 Do not change except when replacing bypass unit Cannot be changed without inputting a password for the reservation code Channel ID number 1 Adjustment value Channel ID number 2 Adjustment value Model FAS 030 2...

Страница 15: ...ck flow The alarm will cease displaying when the actual flow rate becomes within the display range flow rate Registration data abnormal ity 1 Abnormal channel ID numbers registered Correct flow rate calculation cannot be performed The registered channel ID numbers may be wrong Use maintenance mode to register the correct channel ID numbers Note 2 If changing the setting does not clear the alarm tu...

Страница 16: ...mber label of the main channel ー ー Body Number Channel ID number 0 Channel ID number 1 Channel ID number 2 Model numbers are 2 for the FAS 030 3 for the FAS 060 and 4 for the FAS 120 Be sure to double check the channel ID numbers and the model number after you input them 4 Check to make sure that the instantaneous flow rate display shows zero 5 Apply pressure to the flow meter and inside the pipin...

Страница 17: ...01 MPa 1 digit 5 to 100 of FS flow 1 current output 4 to 20 mA Output range 3 2 to 20 8 mA Fixed output during alarm up 21 6 0 4 mA initial default modifiable by setting Fixed output during alarm down 0 0 0 4 mA fixed Allowable load resistance 300 Ωmax Maximum output current 24 mA max Within 1 5 s For 0 100 FS step input time to reach 95 of maximum value Calculation cycle 50 ms Rc 1 4 Rc 1 2 Rc1 R...

Страница 18: ...channel material Bypass unit Gasket Bypass unit case material Load mass kg Semiconductor non volatile memory EEPROM Recorded data Function settings parameters integrated values etc 50 MΩ min Between connector pin and main channel or mounting bolts by 500VDC megger Option with connector oil resistant flame retardant cable UL2464 EN standard See Installation attitudes on page 4 IP65 JISC0920 and IEC...

Страница 19: ...5 0 1 MPa Primary side pressure 0 7 MPa 0 3 MPa 0 5 MPa 0 1000 6000 5000 4000 0 2000 3000 Flow rate R min normal 0 1 MPa Primary side pressure 0 7 MPa 0 3 MPa 0 5 MPa 0 80 20 40 60 Pressure loss kPa Pressure loss kPa FAS 060 20 5 10 15 0 1 MPa Primary side pressure 0 7 MPa 0 3 MPa 0 5 MPa 0 1000 6000 5000 4000 0 2000 3000 Flow rate R min normal 0 1 MPa Primary side pressure 0 7 MPa 0 3 MPa 0 5 MPa...

Страница 20: ...threaded mounting hole 2 M4 x 0 7 depth 7 87 8 90 78 75 63 4 5 5 5 Mounting bracket B FAS 030 FAS 002 2 Rc1 4 FAS 005 2 Rc1 2 threaded mounting hole 2 M4 x 0 7 depth 7 46 5 15 34 75 47 13 5 24 48 27 65 8 1 5 73 8 23 5 IN OUT φ6 90 78 75 63 4 5 5 5 Mounting bracket B M12 connector Cable with connector option 2NL Cable length 2000 mm 5NL Cable length 5000 mm FAS 002 FAS 005 ...

Страница 21: ...th 2000 mm 5NL Cable length 5000 mm φ6 M12 connector threaded mounting hole 2 M5 x 0 8 depth 7 IN OUT FAS 060 2 Rc2 34 17 61 30 5 110 106 8 75 37 5 75 87 5 37 5 Cable with connector option 2NL Cable length 2000 mm 5NL Cable length 5000 mm φ6 M12 connector threaded mounting hole 2 M5 x 0 8 depth 7 OUT IN FAS 120 ...

Страница 22: ...φ4 5 Cross head pan screw M4 0 7 length 6 2 pcs supplied 48 78 90 Additional Parts Dimensions mm φ6 φ14 40 40 FAK 2L 2000 FAK 5L 5000 Bypass unit FAB Mounting bracket B FAS Cable with connector option FAK 2L Cable length 2000 mm Yamatake Corporation FAK 5L Cable length 5000 mm ...

Страница 23: ...tact the Overseas Department below Inquiries Koganei Corporation Overseas Department 3 11 28 Midori cho Koganei City Tokyo 184 8533 TEL 042 383 7172 FAX 042 383 7206 Revision History Ver 2 0 P17 The order codes of Lenght of cable with connector will be changed as bellow 2L 2NL 5L 5NL The order code of cable with connector in additional parts will be changed as below PA5 41S 2MK E FAK 2L PA5 41S 5M...

Страница 24: ...hina Tel 021 6145 7313 Fax 021 6145 7323 KOGANEI PORNCHAI CO LTD 89 174 Moo 3 Vibhavadee Rangsit Road Talad Bangkhen Laksi Bangkok 10210 Thailand Tel 02 551 4025 Fax 02 551 4015 KOGANEI KOREA CO LTD Room 301 Donghwa Bld 25 5 Yoido Yongdeunpo Gu Seoul Korea Tel 02 786 0413 Fax 02 786 0415 For other information and more detailed specifications see the product catalog For inquiries about the product ...

Отзывы: