15
•
Connect the measurement sensor and the evaluation unit to the sensor cable.
Sensor cable
Sensor cable
3.7. Setting the pipe diameter
The flowmeter is factory-set so that the average corrected flow speed is measured in the pipe. The standardized
volumetric flow is calculated by the flowmeter as follows:
V
0
= v
0
* id
2
* π/4 * 3600
V
0
... Standardized volumetric flow [m
3
/h]
v
0
... Standardized flow [m/s]
id ... Internal diameter of pipe [m]
π ... 3,1415
The internal diameter is factory-set to the value acc. table 1.
Because the inner diameter of a pipe is not
standardized and varies depending on wall thickness, the actual inner diameter of the pipe must be set with
the Configurator Software! (see page 35)
Table 1: Factory setting for pipe diameter
da
di
s
Nominal
diameter
External
diameter
wall thick-
ness
internal
diameter
DN
Inch
da (mm/inch) s (mm/inch) di (mm/inch)
50
2"
60.3 / 2.37
2.9 / 0.11
54.5 / 2.15
65
2 1/2" 76.1 / 3.0
2.9 / 0.11
70.3 / 2.77
80
3"
88.9 / 3.5
3.2 / 0.13
82.5 / 3.25
100
4"
114.3 / 4.5
3.6 / 0.14
107.1 / 4.22
125
5"
139.7 / 5.5
4.0 / 0.16
131.7 / 5.19
150
6"
168.3 / 6.63
4.5 / 0.18
159.3 / 6.27
200
8"
219.1 / 8.63
6.3 / 0.25
206.5 / 8.13
250
10"
273.0 / 10.75
6.3 / 0.25
260.4 / 10.25
300
12"
323.9 / 12.75
7.1 / 0.28
309.7 / 12.19
350
14“
355,6 / 14.00
8 / 0.31
339,6 / 13.37
400
16“
406,4 / 16.00
8,8 / 0.35
388,8 / 15.31
500
20“
508 / 20.00
11 / 0.43
486 / 19.13
600
24“
610 / 24.00
12,5 / 0.49
585 / 23.03
700
28“
711 / 28.00
14,2 / 0.56
682.6 / 26.87