OPERATING MANUAL HPC & UMC4
Page 79 of 105
14.10.3 Current output I1 assignment
This function allows the operator to define the measured value to be output as an analog signal via cur-
rent output I1. When devices with HART
®
communication capabilities are used, current output I1 is usual-
ly assigned to mass flow. Press
„Enter“ to display the current setting.
I1 assigned to
[Mass flow]
As mentioned in Section 13.4.3.1 Selection window/make a selection, the operator can choose between
the following settings:
Mass flow
Volume flow
Density
Temperature
14.10.4 Current output I2 4 to 20 mA
The “Current output I2 4 to 20 mA” function allows the operator to define the range in which the current
output is to be operated. The range from 4 to 20.5 mA follows the NAMUR recommendation and covers
the range from 0 to 104 % of the measuring range. The standard range from 4 to 21.6 mA allows for a
control of the measuring range of up to 110 %.
Press
„Enter“ to display the current setting.
Current output I2
[4]
– 21.6 mA
As mentioned in Section 13.4.3.1 Selection window/make a selection, the operator can choose between
the following settings:
14.10.5 Current output I2 alarm
This function allows the operator to define the state taken on by the current output when a state of alarm
is detected. This information can be analyzed in the control system. Press
„Enter“ to display the current
setting.
I2 : alarm
[not used]
As mentioned in Section 13.4.3.1 Selection window/make a selection, the operator can choose between
the following settings:
not used
no alarm function
> 22 mA
current rise in the case of an alarm
< 3.8 mA
current reduction in the case of an alarm