37
LINE:
Connect terminals 1 and 2 to the electrical power supply.
(terminals already connected to power supply cable in the factory)
AUX
: This is used to control a boiler coupled with the heating system
where present. Connect terminals 4 and 5 (or 3 and 4 depending on the
type of connection to the coupled boiler) to the TA (Room Thermostat)
contact on the boiler. It is then possible to control the coupled boiler
using the temperature set on the
AUX thermostat
; above the set
temperature the coupled boiler turns off and comes on again only below
the set temperature.
VALVE:
Connect terminals 6, 7 and 8 to the 3-way motorised valve.
This is used to control a motorised 3-way valve (or two 2-way motorised
valves) installed on the dhw system. The valve opens the circuit at
temperatures higher than those set on the
VALVE thermostat
(230V
voltage on terminals 6 and 7) and closes the circuit at lower
temperatures (230V voltage on terminals 7 and 8). (Terminals already
connected at the factory to a cable suitable for connection to a 3-way
valve -
see page 34
).
SERV:
Additional thermostat supplied at 230V. Connect terminals 9 and
10. This can be useful, for example, for controlling an additional pump
installed on the system. The additional pump will operate at
temperatures higher than those set on the
SERV thermostat
. We
recommend setting the
SERV thermostat
to temperatures higher than
55°C to prevent condensation, which would damage the heating cooker's
boiler unit, from forming.
PUMP:
Connect terminals 13 and 14 to the pump on the heating system.
This is used to control the pump installed on the heating system. The
heating pump will operate at temperatures higher than those set on the
PUMP thermostat
. We recommend setting the pump thermostat to
temperatures higher than 55°C to prevent condensation, which would
damage the heating cooker's boiler unit, from forming.
(Terminals already
connected to pump cable in the factory).
PROBE:
Connect the water temperature probe to terminals 18 and 19.
This is used to detect the water temperature inside the heating cooker. If
the probe is not connected, the control unit's display shows
“Lo”
; if the
probe is short-circuited, the display shows
“Hi”.
(Terminals already
connected to Water Probe in the factory).
Содержание K top
Страница 1: ...INSTALLATION USE AND MAINTENANCE USEFUL ADVICE Heating cooker Heating stove User guide EN...
Страница 2: ...2...
Страница 5: ...5 HEATING COOKERS and HEATING STOVES models K top KP top and models TS top TSP top S R L...
Страница 15: ...15 Top view of heating stove 600 665 622 275 515 170 150...
Страница 49: ...49 Loosen the two hex screws on the inspection vent 1 2...
Страница 50: ...50 Remove the vent as shown in the diagram and remove any deposits under the oven...
Страница 63: ...63...