59
4
Quadrant
Energy Analyzer
4
Quadrant
Energy Analyzer
SECTION 3 MENUS
Invalid limits!
Please check.
Settings->Setup->Alarm->Current
Alarm relay
Relay1
Low limit
0.0
A
Hysteresis
0.0
%
High limit
0.0
A
Delay 0.0
sec
OK
X
Fig. 3-54 Invalid Limits message
3.2.1.1.8.12 Harmonics V Menu
Inside ‘Alarm’ menu, when Harmonics V is highlighted, press OK key and the following
page will appear on the screen.
Settings->Setup->Alarm->Harmonics V
Alarm relay
Off
THDV hi limit
0.0
%
V3 hi limit
0.0
%
V5 hi limit
0.0
%
V7 hi limit
0.0
%
V9 hi limit
0.0
%
V11 hi limit
0.0
%
V13 hi limit
0.0
%
V15 hi limit
0.0
%
V17 hi limit
0.0
%
V19 hi limit
0.0
%
V21 hi limit
0.0
%
Delay
60
sec
Fig. 3-55 Harmonics Menu
Alarm relay:
Refer to
- Menu - Alarm relay setting.
THDV High Limit:
High limit value for total harmonic distortion - voltage alarm (For Virtual Keyboard
. In order to set an alarm for THDV, operator should enter a high limit
value larger than zero. When high limit is entered as zero, THDV alarm will be deactivated
(no alarm will be set). It can be adjusted between 0 100.
Содержание Klea 320P-D
Страница 1: ...1 4Quadrant Energy Analyzer 1 KLEA Network Analyzer User Manual 4Quadrant Energy Analyzer...
Страница 8: ...8 4Quadrant Energy Analyzer SECTION 1 GENERAL INFORMATION 4Quadrant Energy Analyzer...
Страница 14: ...14 4Quadrant Energy Analyzer SECTION 2 INSTALLATION 4Quadrant Energy Analyzer...
Страница 21: ...21 4Quadrant Energy Analyzer SECTION 3 MENUS 4Quadrant Energy Analyzer...
Страница 82: ...82 4Quadrant Energy Analyzer SECTION 4 MODBUS PROTOCOL 4Quadrant Energy Analyzer...
Страница 119: ...119 4Quadrant Energy Analyzer SECTION 5 FACTORY DEFAULT SETTINGS 4Quadrant Energy Analyzer...
Страница 123: ...123 4Quadrant Energy Analyzer SECTION 6 TECHNICAL SPECIFICATIONS 4Quadrant Energy Analyzer...