1.7 Four-Quadrant Represantation
The angle(Ø) between voltage and current provides us information about the direction of
energy fl w. A positive sign for active/reactive power indicates that active/reactive power
is consumed. And also a negative sign for active/reactive power indicates that active/
reactive power is generated.
Meters
Imp. Active &
Ind. Reactive
Active Power
Reactive Power
Meters
Exp. Active &
Ind. Reactive
QUADRANT -1
P => positive
Q => positive & inductive
CosØ => inductive
PF => positive
QUADRANT -2
P => negative
Q => positive & capacitive
CosØ => capacitive
PF => negative
Meters
Imp. Active &
Cap. Reactive
Meters
Exp. Active &
Cap. Reactive
QUADRANT -4
P => positive
Q => negative & capacitive
CosØ => capacitive
PF => positive
QUADRANT -3
P => negative
Q => negative & inductive
CosØ => inductive
PF => negative
S
P
Q
Fig. 1-2 Four-Quadrant Representation
NOTE:
If the signs of active and reactive power are examined, it can be defined the
quadrant that Klea measures.
E.g.;
P= +10kWh,Q= +5kVAr
=>
Quadrant-1
P= -10kWh, Q= +5VAr
=>
Quadrant-2
P= -10kWh, Q= -5kWh
=>
Quadrant-3
P= +10kWh,Q=-5kWh
=>
Quadrant-4
SECTION 1 GENERAL INFORMATION
Содержание Klea 320P-D
Страница 1: ...1 4Quadrant Energy Analyzer 1 KLEA Network Analyzer User Manual 4Quadrant Energy Analyzer...
Страница 8: ...8 4Quadrant Energy Analyzer SECTION 1 GENERAL INFORMATION 4Quadrant Energy Analyzer...
Страница 14: ...14 4Quadrant Energy Analyzer SECTION 2 INSTALLATION 4Quadrant Energy Analyzer...
Страница 21: ...21 4Quadrant Energy Analyzer SECTION 3 MENUS 4Quadrant Energy Analyzer...
Страница 82: ...82 4Quadrant Energy Analyzer SECTION 4 MODBUS PROTOCOL 4Quadrant Energy Analyzer...
Страница 119: ...119 4Quadrant Energy Analyzer SECTION 5 FACTORY DEFAULT SETTINGS 4Quadrant Energy Analyzer...
Страница 123: ...123 4Quadrant Energy Analyzer SECTION 6 TECHNICAL SPECIFICATIONS 4Quadrant Energy Analyzer...