KLEA is connected to current transformer(s). Before disconnecting
current transformer leads, be sure that they are short circuited elsewhere
or connected to a parallel load which has sufficie tly low impedance.
Otherwise dangerously high voltages will be induced at the current
transformer leads. Same phenomena also apply for putting into service.
The cable is placed into the related opening.
Fig. 2-4 Inserting Cable into the Terminal Block
After the cable is placed, the screws are tightened and the cable is fixed.
Fig. 2-5 Fixing the Cable to the Terminal Block
The Terminal Block is inserted into its seat located on KLEA.