55
4
Quadrant
Energy Analyzer
4
Quadrant
Energy Analyzer
SECTION 3 MENUS
3.2.1.1.8.1 V(L-N) Menu
Inside‘Alarm’ menu, when V(L-N) is highlighted, press OK key and the following page will
appear on the screen.
Settings->Setup->Alarm->V(L-N)
Alarm relay
Off
Low limit
0.0
V
High limit
0.0
V
Delay
0 sec
Hysteresis 0.0
%
Fig. 3-48 V(L-N) Menu
Alarm relay :
This setting is merely used to energize or not to energize a relay, when an alarm occurs.
For alarm relay setting, following options are available:
Off
: In case of V(L-N) alarm, none of the alarm relaysis energized
Relay1
: In case of V(L-N) alarm, relay 1 is energized
Relay2
: In case of V(L-N) alarm, relay 2 is energized
Press up and down keys to select the desired option and press OK key to complete the
setting.
Alarm relay
Off
Fig. 3-49 Alarm Relay Setup
In order to adjust Klea to issue V (L-N) alarms, operator should adjust low limit and high
limit values as described below.
When V(L-N) of “any” of the three phases exceeds “Low limit” or “High Limit”, Klea gives
an alarm.
Содержание Klea 320P-D
Страница 1: ...1 4Quadrant Energy Analyzer 1 KLEA Network Analyzer User Manual 4Quadrant Energy Analyzer...
Страница 8: ...8 4Quadrant Energy Analyzer SECTION 1 GENERAL INFORMATION 4Quadrant Energy Analyzer...
Страница 14: ...14 4Quadrant Energy Analyzer SECTION 2 INSTALLATION 4Quadrant Energy Analyzer...
Страница 21: ...21 4Quadrant Energy Analyzer SECTION 3 MENUS 4Quadrant Energy Analyzer...
Страница 82: ...82 4Quadrant Energy Analyzer SECTION 4 MODBUS PROTOCOL 4Quadrant Energy Analyzer...
Страница 119: ...119 4Quadrant Energy Analyzer SECTION 5 FACTORY DEFAULT SETTINGS 4Quadrant Energy Analyzer...
Страница 123: ...123 4Quadrant Energy Analyzer SECTION 6 TECHNICAL SPECIFICATIONS 4Quadrant Energy Analyzer...