112
4
Quadrant
Energy Analyzer
4
Quadrant
Energy Analyzer
SECTION 4 MODBUS PROTOCOL
E.g.:
If slave ID is assigned as 157;
Request
KLEA Response
Slave ID
01h
Slave ID
01h
Function code
10h
Function code
10h
Starting address (high)
08h
Starting address (high)
08h
Starting address (Low )
26h
Starting address (Low )
26h
Number of registers (high)
00h
Number of registers (high)
00h
Number of registers (Low )
02h
Number of registers (Low )
02h
Number of bytes
04h
CRC(high)
A2h
Register value (high)
00h
CRC(Low )
63h
Register value (Low )
00h
Register value (high)
00h
Register value (Low )
9Dh
CRC(high)
D7h
CRC(Low )
F4h
4.5.3 ARCHIVE (HISTORY) RECORDS
Archive records consist of blocks having 68 parameters. Each parameter inside the
archive block is a 32 bit length variable. Archive data block is as shown in
The programmer will access archive by implementing“0x14 - Read File Record”
function. “0x14 - Read File Record” function accesses the data with “file numbers”.
For Klea,
File numbers 1 – 1920 are used to access HOURLY data. File numbers 5001- 5240 are
used to access DAILY data. File numbers 10001-10036 are used to access MONTHLY
data.
• The last saved file number in the hourly data memory; can be accessed from 1360
Modbus addressed parameter
• The last saved file number in the daily data memory; can be accessed from 1362
Modbus addressed parameter
• The last saved file number in the monthly data memory; can be accessed from 1364
Modbus addressed parameter
Содержание Klea 320P-D
Страница 1: ...1 4Quadrant Energy Analyzer 1 KLEA Network Analyzer User Manual 4Quadrant Energy Analyzer...
Страница 8: ...8 4Quadrant Energy Analyzer SECTION 1 GENERAL INFORMATION 4Quadrant Energy Analyzer...
Страница 14: ...14 4Quadrant Energy Analyzer SECTION 2 INSTALLATION 4Quadrant Energy Analyzer...
Страница 21: ...21 4Quadrant Energy Analyzer SECTION 3 MENUS 4Quadrant Energy Analyzer...
Страница 82: ...82 4Quadrant Energy Analyzer SECTION 4 MODBUS PROTOCOL 4Quadrant Energy Analyzer...
Страница 119: ...119 4Quadrant Energy Analyzer SECTION 5 FACTORY DEFAULT SETTINGS 4Quadrant Energy Analyzer...
Страница 123: ...123 4Quadrant Energy Analyzer SECTION 6 TECHNICAL SPECIFICATIONS 4Quadrant Energy Analyzer...