15
Power range [kW]
"A" - minimum di-
stance
[cm]
4-16
25-35
5-20
6-26
8-36
10-50
35-45
After connecting and starting the burner, the technician should train the user for the
correct operation of the device, refer to possible controller settings and behaviour in case of
an emergency and how to eliminate it.
The boiler room should meet certain conditions regarding the safety and protection of
fire protection. In particular, there should not be stored flammable materials and substances.
The ventilation system should meet the minimum requirements specified in the following
table:
Power range [kW]
Cross section of the
air supply [cm
2
]
(Diameter [cm])
Cross section of the
exhaust air cord [cm
2
]
(Diameter [cm])
up to 30
200 (ø16)
200 (ø16)
30-60
300 (ø20)
200 (ø16)
60-2000
5 cm
2
per 1 kW of power,
not less than 300 cm
2
equal to at least the mid-
section of the supply cable,
not less than 200 cm
2
Position of the central heating boiler in the boiler room shall be in accordance with the
guidelines specified in the boiler manufacturer's instructions. Leave at least 30 cm of free
space around the burner; More space will facilitate maintenance and cleaning the burner and
removal of ash from the device. Leave at least 10 cm of free space under the burner - to avoid
blocking the air inlet of the fan. Pellet tray should be positioned at least 15 cm away from the
boiler and at least 10 cm from the walls. In this case, consider the location of the tray to en-
sure easy refuelling.
The central heating should be filled in the required range - i.e. should have appropriate
pressure and the value shall be specified in the boiler's instruction manual. This installation
should be vented.
It is forbidden to use the igniter without safety guards.
Содержание ROT-POWER 10-50 kW
Страница 5: ...5 Fig 1 Block diagram of the burner ...
Страница 9: ...9 Fig 2 Components of the set ...
Страница 22: ...22 Fig 8 Cleaning the tubular blower chamber view 1 ...
Страница 23: ...23 Fig 9 Cleaning the tubular blower chamber view 2 ...
Страница 27: ...27 Fig 11 Lubricating the bearings of the combustion chamber view 1 ...
Страница 28: ...28 Fig 12 Lubricating the bearings of the combustion chamber view 2 ...
Страница 30: ...30 Fig 13 Igniter Replacement ...
Страница 34: ...34 12 2 Electric diagram of the burner Fig 15 Wiring diagram of the burner where ...