ZDV3318 / MQZDV3318 - Clearance to Combustibles
Clearance to Combustibles
Back (from Standoffs)
0 inches/0 mm
Side (from standoffs)
0 inches/0 mm
Floor
0 inches/0 mm
Ceiling (from bottom of fireplace) 60 inches/152 cm
Top (from standoffs)
0 inches/0 mm
Louvered Unit
Top of 90 degree bend in Minimum Enclosure of:
37 3/4 to 40 inches
3 1/4 inches/8.3 cm / All Vent Systems
Enclosure over 40 inches
2 1/2 inches/6.4 mm/All Vent Systems
CVCK Unit (non-louvered)
Top of 90 degree bend in Minimum Enclosure of:
40.5inches to 43 inches 5 inches/12.7 cm / All Vent Systems
Enclosure over 43inches 2 1/2 inches/6.4 cm All Vent Systems
Systems
Top of Horizontal Pipe
1 1/2 inches/3.8 cm / All Vent Systems
Side & Bottom of Horizontal Pipe 1 inch/25.5mm / All Vent Systems
Vertical Vent Pipe
1 inch/25.5mm / Kingsman Vent Systems
Vertical Vent Pipe
1 1/4 inch/32mm / All Hard Pipe Systems
(NOTE -Floor) if installing the
appliance directly on
carpeting or other combustible
materials other than wood
flooring, the appliance shall be
installed on a metal or wood
panel, the full width and depth
of the appliance. Carpet may
extend 1 inch above the floor
of appliance.
For units with CVCK (Clear
View Circulating Kit) see
framing with CVCK to
establish floor heights
17