Chapter 3: Configuration and commissioning
KFP-CE4 Series Installation Manual
53
Examples:
•
A conventional repeater panel can repeat an analogue panel and many
indications are not available for display.
•
A two-
zone
fire control panel could be configured to repeat a four-
zone
evacuation panel. Zones 3 and 4 from the evacuation panel will not be
available for display.
Conventional systems can be configured to repeat control panels status
information instead of zones status information, in the zone LED indications.
Consult the Repe
ater type configuration (nr) setting.
Selecting control panel commands
Select the control panel commands (e.g. reset, silence/resound sounders, panel
silence, cancelling delays) that will be local or global. This i
s sent to all other
control panels in its firenet map.
By default, nC is set to Yes so that controls are local but also sent to the network.
Note:
Local or global controls does not apply to disable/enable and test
commands. These are always local and sent to the control panels being
repeated. This feature provides more flexibility to configure disable/enable and
test of zones, sounders, fire routing and fire protection.
Examples: If we disable zone 1 in control panel 1 and control panel 1 repeats
control pa
nel 2, the zone 1 in control panel 2 will also be disabled (shared zone
completely disabled). If we disable zone 1 in control panel 1 but control panel 2 is
not repeated, zone 1 in panel 2 will not be disabled. (This allows disabling only
part of the share
d zone).
Selecting the loop class
Select the loop class (nL) to configure the panel according to the wiring topology
selected: class A (ring) or class B (bus).
Class A is recommended to provide redundancy in communication path. Class B
can only be used for repeaters without control requirements.
By default, the basic settings use class B for basic repeater functionality.
Selecting processing for remote zones in alarm
S
elect the setting to process (or not process) remote zones in alarm (nP).
This setting lets you decide whether the control panel enters alarm and reacts
accordingly or not, with any remote zone outside its range of zones. This option
lets you:
•
Create lar
ge conventional systems (e.g. 10, 12, 16 or more zones) where
each node has different global zones to indicate only the local zone in alarm
•
Create systems where alarm indications have to be local to the panel (nP
should be inactive)
By default, process remote zone alarms (nP) is active (ON).
Содержание KFP-CE4 Series
Страница 1: ...KFP CE4 Series Installation Manual P N 501 415503 1 31 REV 03 10 ISS 08NOV13 ...
Страница 6: ...iv KFP CE4 Series Installation Manual ...
Страница 10: ...Chapter 1 Introduction 4 KFP CE4 Series Installation Manual ...
Страница 64: ...Chapter 3 Configuration and commissioning 58 KFP CE4 Series Installation Manual ...
Страница 68: ...Chapter 4 Maintenance 62 KFP CE4 Series Installation Manual ...
Страница 76: ...Chapter 5 Technical specifications 70 KFP CE4 Series Installation Manual Figure 21 Cabinet without cover ...
Страница 86: ...Appendix A Configuration presets 80 KFP CE4 Series Installation Manual ...
Страница 90: ...Appendix B Product compliance 84 KFP CE4 Series Installation Manual ...