Chapter 3: Configuration and commissioning
KFP-CE4 Series Installation Manual
43
Display
Description
Fire routing inhibit delay
Input active deactivates fire routing delays.
Class change
Sounders are activated while the input is active
Fault warning output open supervision
An inactive input indicates the fault warning output has
an open circuit wiring fault.
Fire routing acknowledgement (type 1, 100 seconds) [1]
[2]
An active input indicates acknowledge after fire routing is
active. An active input in other condition generates a fire
routing fault.
Fire routing acknowledgement (type 2, 240 seconds) [1]
[2]
An active input indicates acknowledge after fire routing is
active. An active input in other condition generates a fire
routing fault.
[1] Can be configured for only one input per control panel.
[2] Supervision for wiring open and short conditions is
available. A 15 kΩ
end-of-line is required.
Changing user level passwords
Use the corresponding menu option (shown below) to change the default user
level passwords.
Operator user level password
Basic installer user level password
Advanced installer user level password
To change the first two digits of a user level password:
1. Set the
display for the desired user level password, and then press Enter.
2.
Set the display as shown below, and then press Enter.
3. Select a value using the value selection buttons (2 and 4).
4. Press Enter.
Содержание KFP-CE4 Series
Страница 1: ...KFP CE4 Series Installation Manual P N 501 415503 1 31 REV 03 10 ISS 08NOV13 ...
Страница 6: ...iv KFP CE4 Series Installation Manual ...
Страница 10: ...Chapter 1 Introduction 4 KFP CE4 Series Installation Manual ...
Страница 64: ...Chapter 3 Configuration and commissioning 58 KFP CE4 Series Installation Manual ...
Страница 68: ...Chapter 4 Maintenance 62 KFP CE4 Series Installation Manual ...
Страница 76: ...Chapter 5 Technical specifications 70 KFP CE4 Series Installation Manual Figure 21 Cabinet without cover ...
Страница 86: ...Appendix A Configuration presets 80 KFP CE4 Series Installation Manual ...
Страница 90: ...Appendix B Product compliance 84 KFP CE4 Series Installation Manual ...