Chapter 2: Installation
16
KFP-CE4 Series Installation Manual
Input function
Input
Value
[1]
State
Fault warning output: open circuit
supervision [4]
2
≤ 9 kΩ
Standby
> 9 kΩ
Fault (open)
[1] Values between each state may vary, depending on tolerance.
[2] For EN 54-
13 compliance, the active impedance should be in the range of 220 Ω to 3.9 kΩ.
[3] High impedance fault.
[4] For the open circuit s
upervision of the fault warning output with the input, a 2010
-FS EOL
board must be installed. See “
Connecting the fault warning output” on page 18.
Connecting supervised outputs
The evacuation control panel has six out
puts, marked OUT1 through OUT6
.
The outputs are supervised for open and short circuit faults.
Output class
The evacuation control panel outputs can be configured for Class A or Class B
operation, depending on the supervision mode required. The default output
configuration is Class B.
Table 9: Output classes and EN 54-13 supervision
Output class
EN 54-13 supervision
Description
Class B (default)
Disabled
For installations not requiring EN 54-13
compliance
Class A
Enabled
For installations requiring EN 54-13
compliance
For more information, see “
EN 54-13 supervision mode” on page 32.
Output functionality
The function of each output is defined by the panel operating mode and output
class configuration (the default is Class B). All outputs are overload protected.
Table 10: Class B output functionality (default)
Operating mode OUT1
OUT2
OUT3
OUT4
NEN 2575 with
four evacuation
areas
Evacuation
sounders for
zone 1
Evacuation
sounders for
zone 2
Evacuation
sounders for
zone 3
Evacuation
sounders for
zone 4
NEN 2575 with
two evacuation
areas
Evacuation
sounders for
zone 1
or
zone 2
Evacuation
sounders for
zone 1
or
zone 2
Evacuation
sounders for
zone 3
or
zone 4
Evacuation
sounders for
zone 3
or
zone 4
NEN 2575 with
one evacuation
area
Evacuation
sounders for any
zone
Evacuation
sounders for any
zone
Evacuation
sounders for any
zone
Evacuation
sounders for any
zone
Содержание KFP-CE4 Series
Страница 1: ...KFP CE4 Series Installation Manual P N 501 415503 1 31 REV 03 10 ISS 08NOV13 ...
Страница 6: ...iv KFP CE4 Series Installation Manual ...
Страница 10: ...Chapter 1 Introduction 4 KFP CE4 Series Installation Manual ...
Страница 64: ...Chapter 3 Configuration and commissioning 58 KFP CE4 Series Installation Manual ...
Страница 68: ...Chapter 4 Maintenance 62 KFP CE4 Series Installation Manual ...
Страница 76: ...Chapter 5 Technical specifications 70 KFP CE4 Series Installation Manual Figure 21 Cabinet without cover ...
Страница 86: ...Appendix A Configuration presets 80 KFP CE4 Series Installation Manual ...
Страница 90: ...Appendix B Product compliance 84 KFP CE4 Series Installation Manual ...