Chapter 2: Installation
14
KFP-CE4 Series Installation Manual
The panel supports conventional detectors. To guarantee optimal operation, use
the detectors specified in the compatibility list. For more information on fire
detectors, see
Chapter 5
“
Technical specifications”
on page 63
.
Connecting manual call points
Connect manual call points in parallel, as shown in
Figure 4
,
Figure 5
,
Figure
6,
and Figure 7 starting on page 11
. Each zone circuit can support up to 32 manual
call points.
Manual call points must have a resistance installed in series with the normally
open (NO) contact to avoid short-circuit faults and to allow the control panel to
identify the origin of the alarm (automatic or manual). Note that many of the
MCPs in the compatibility list already include this resistor.
The resistance required will depend on the zone type as shown
in Table 5 below.
Table 5: MCP resistances
Zone type
Manual call point resistance
[1]
Standard / active end-of-
line
EN 54-13
Intrinsically safe
Mixed
100 Ω
Not supported
Not supported
Manual
100 to 680 Ω
100 to 470 Ω
250 to 560 Ω
[1] Resistance must be rated at 1 W minimum.
Note:
The default zone detection settings for each operating mode can be found
in Appendix A
“
Configuration presets” on page 71
. To change the zone detection
setting, see “
Advanced configuration”
on page 36
.
Connecting inputs
Input functionality
Each control panel has two inputs, marked INPUT1 and INPUT2. These circuits
are connected as normally open and activated when closed.
Both inputs are configurable (see
“
Input configuration” on page 42). The default
functionality of each input is defined by the panel operating mode and EN 54-13
configuration. See Table
6
below.
Table 6: Default input functionality for inputs 1 and 2
Operating mode
INPUT1
INPUT2
NEN 2575 (EN 54-13 disabled) Fire routing inhibit delay
Delay off
NEN 2575 (EN 54-13 enabled) Fire routing acknowledgement
(type 1
, 100 seconds)
Fault warning output (open
supervision)
Содержание KFP-CE4 Series
Страница 1: ...KFP CE4 Series Installation Manual P N 501 415503 1 31 REV 03 10 ISS 08NOV13 ...
Страница 6: ...iv KFP CE4 Series Installation Manual ...
Страница 10: ...Chapter 1 Introduction 4 KFP CE4 Series Installation Manual ...
Страница 64: ...Chapter 3 Configuration and commissioning 58 KFP CE4 Series Installation Manual ...
Страница 68: ...Chapter 4 Maintenance 62 KFP CE4 Series Installation Manual ...
Страница 76: ...Chapter 5 Technical specifications 70 KFP CE4 Series Installation Manual Figure 21 Cabinet without cover ...
Страница 86: ...Appendix A Configuration presets 80 KFP CE4 Series Installation Manual ...
Страница 90: ...Appendix B Product compliance 84 KFP CE4 Series Installation Manual ...