Chapter 2: Installation
KFP-CE4 Series Installation Manual
9
Menu inserts
The last step in installing the cabinet is to apply the menu insert that corresponds
to the intended system configuration.
The default configuration does not use EN 54-
13 zone supervision.
For this
configuration,
use the printed insert identified as NEN2575.
If the panel will be configured to use EN 54-
13 zone supervision,
the
corresponding insert includes a label for the Fault Output Fault/Disabled LED.
Use the printed insert identified as NEN2575 - EN 54-13.
To apply the menu inserts:
1.
Add the detection zone
names and evacuation area names to the top insert
segment.
Detection zone names go in the left column. Evacuation area names go in the
right column, above the preprinted LED label text.
2.
Detach the four insert segments from the sheet.
3.
Remove the control panel cover
.
4.
Insert each segment in the appropriate slot, as shown in
Figure 3 below.
Make sure that the inserts are positioned correctly.
5.
Replace the
control panel cover.
Figure 3: Applying the menu inserts
Содержание KFP-CE4 Series
Страница 1: ...KFP CE4 Series Installation Manual P N 501 415503 1 31 REV 03 10 ISS 08NOV13 ...
Страница 6: ...iv KFP CE4 Series Installation Manual ...
Страница 10: ...Chapter 1 Introduction 4 KFP CE4 Series Installation Manual ...
Страница 64: ...Chapter 3 Configuration and commissioning 58 KFP CE4 Series Installation Manual ...
Страница 68: ...Chapter 4 Maintenance 62 KFP CE4 Series Installation Manual ...
Страница 76: ...Chapter 5 Technical specifications 70 KFP CE4 Series Installation Manual Figure 21 Cabinet without cover ...
Страница 86: ...Appendix A Configuration presets 80 KFP CE4 Series Installation Manual ...
Страница 90: ...Appendix B Product compliance 84 KFP CE4 Series Installation Manual ...