Chapter 3: Configuration and commissioning
KFP-A Series Installation Manual
91
8. Press F1 (Save), F3 (Apply), F4 (Discard), or F2 (Exit).
Remember to apply saved settings from the Main menu.
Output group activation
Output groups can be activated by any of the following:
•
Zone activation with delays
•
Output group confirmation for specific outputs (EN 54-2 type C)
•
Logic rules (configured via the configuration utility PC application)
•
Manual activation by programmable start/stop buttons (evacuation panels
only)
To avoid unexpected alarm behaviour, consider the activation options when
configuring your fire system. If zone activation is not programmed correctly then
a zone in alarm could override any required confirmation configuration of an
output group.
Delayed output group activation with alarm confirmation
Note:
This option is compliant with EN 54 type C alarm confirmation.
Activation of control panel output groups can be delayed based on alarm
confirmation configuration (this may be used, for example, with outputs for
extinguishing devices). The maximum configurable delay is 999 seconds.
The output group alarm confirmation configuration options are shown in the table
below.
Note:
Configuration requires that two independent alarm confirmations be
selected from the available options and that a confirmation delay (in seconds) is
entered for the corresponding output group to be activated.
Table 54: Output group alarm confirmation options
Option
Description
DEV l.ddd
An alarm activated by a predefined loop and addressable device, where “l”
is the loop number and “ddd” is the device address
ZONE zzzz
An alarm activated by a predefined global zone, where “zzzz” is the global
zone number (from 1 to 9999)
PANEL pp
An alarm activated by a predefined control panel, where “pp” is the control
panel network node ID
ALWAYS
If only a single alarm event with confirmation delay is required (for example
for a manual call point zone), select the corresponding first alarm event, and
then select this option for the second alarm
Содержание KFP-AE1(-S)
Страница 1: ...KFP A Series Installation Manual P N 00 3252 501 0003 04 ISS 04MAY15...
Страница 6: ...iv KFP A Series Installation Manual...
Страница 20: ...Chapter 1 Introduction 14 KFP A Series Installation Manual...
Страница 113: ...Chapter 3 Configuration and commissioning KFP A Series Installation Manual 107...
Страница 114: ......
Страница 126: ...Chapter 5 Technical specifications 120 KFP A Series Installation Manual Figure 27 Large cabinet dimensions and views...
Страница 127: ...Chapter 5 Technical specifications KFP A Series Installation Manual 121 Figure 28 Small cabinet dimensions and views...
Страница 128: ...Chapter 5 Technical specifications 122 KFP A Series Installation Manual...
Страница 142: ...Appendix C Menu maps 136 KFP A Series Installation Manual...
Страница 148: ......