Chapter 3: Configuration and commissioning
98
KFP-A Series Installation Manual
5. If warning tones are required (for second stage sounders), select Warning
time, and then enter the time value (in seconds).
Check the WrnT_4E check box to change from the warning tone to
evacuation tone only if a manual call point alarm is detected.
If a delay is required before the warning tone begins, configure the warning
delay for the corresponding output group.
See “Warning time” on page 100 for more information on this option.
6. Select Sounders silence disable time, and then enter the value (in seconds).
The default delay is 60 seconds. The minimum delay is 0 seconds (this
configuration is not recommended). The maximum delay should be lower than
the minimum configured sounders delay.
See “Sounders silence disable time” on page 101 for more information on this
option.
7. Press F4 (Enter), and then press F1 (Back).
8. Press F1 (Save), F3 (Apply), F4 (Discard), or F2 (Exit).
Remember to apply saved settings from the Main menu.
Investigation mode
Select Investigation mode to define a regional investigation mode for the control
panel. The available options are shown in the table below. The default setting is
NO (no investigation mode is required).
Note:
For fire routing investigation modes, in the event of several fire routing
groups, the extended delay applies only to the groups in delay when the alarm is
acknowledged by the user.
Table 58: Regional investigation time modes
Setting
Description
NO (default)
No investigation mode is required.
MAX_ACK_T
Maximum acknowledgement time.
The configured investigation time starts to count down when the
control panel reports a detector alarm.
If the alarm is acknowledged during the investigation time (by
pressing the Panel Silence button), then any sounder or fire routing
delays continue to be processed as configured. If a new zone
reports an alarm after the control panel is silenced, the panel starts
another acknowledgement time period.
If the alarm is not acknowledged during the investigation time (by
pressing the Panel Silence button), then sounders and fire routing
are activated when the configured investigation time elapses.
Содержание KFP-AE1(-S)
Страница 1: ...KFP A Series Installation Manual P N 00 3252 501 0003 04 ISS 04MAY15...
Страница 6: ...iv KFP A Series Installation Manual...
Страница 20: ...Chapter 1 Introduction 14 KFP A Series Installation Manual...
Страница 113: ...Chapter 3 Configuration and commissioning KFP A Series Installation Manual 107...
Страница 114: ......
Страница 126: ...Chapter 5 Technical specifications 120 KFP A Series Installation Manual Figure 27 Large cabinet dimensions and views...
Страница 127: ...Chapter 5 Technical specifications KFP A Series Installation Manual 121 Figure 28 Small cabinet dimensions and views...
Страница 128: ...Chapter 5 Technical specifications 122 KFP A Series Installation Manual...
Страница 142: ...Appendix C Menu maps 136 KFP A Series Installation Manual...
Страница 148: ......