Chapter 3: Configuration and commissioning
100
KFP-A Series Installation Manual
Note:
The table above indicates the minimum and maximum values when
Inv_Ack is not enabled (any configured investigation time starts when the alarm
is detected). If Inv_Ack is enabled, the maximum investigation time is 600
seconds less the configured investigation time, and the minimum is 0.
Warning time
Select Warning time to configure a warning time for applications with warning
tone requirements (second stage sounders).
Note:
If a warning delay is required, this must be configured separately (see
“Sounder, fire routing, fire protection, and program output group delays” on page
94).
With this option, sounders emit the warning tone for a configured period of time
(the warning time). When the warning time ends, the sounder tone changes to
the evacuation tone (the warning tone continues to sound for the duration of any
configured delay that precedes the evacuation tone). See Figure 24 and
Figure 25 on page 101, below, for examples of delays with and without second
stage requirements.
Note:
The sounder tones are configured in the corresponding device
configuration screen.
There are three configurable time periods, as shown in the table below.
Table 60: Warning time, warning delay, and delay
Time period
Description
Warning time
The time from when the alarm is reported until the sounders activate
the evacuation tone (or the corresponding evacuation tone delay
starts to count down)
Warning delay [1]
The optional delay before the sounders activate the warning tone
Delay [1]
The optional delay before the sounders activate the evacuation tone
[1] To configure these values, see “Sounder, fire routing, fire protection, and program output
group delays” on page 94.
Figure 24: Detector alarm with second stage delay
Warning tone
Evacuation tone
Warning time (or
second stage delay)
Warning delay
Delay
D
et
ec
tor
al
ar
m
R
es
et
Time
Содержание KFP-AE1(-S)
Страница 1: ...KFP A Series Installation Manual P N 00 3252 501 0003 04 ISS 04MAY15...
Страница 6: ...iv KFP A Series Installation Manual...
Страница 20: ...Chapter 1 Introduction 14 KFP A Series Installation Manual...
Страница 113: ...Chapter 3 Configuration and commissioning KFP A Series Installation Manual 107...
Страница 114: ......
Страница 126: ...Chapter 5 Technical specifications 120 KFP A Series Installation Manual Figure 27 Large cabinet dimensions and views...
Страница 127: ...Chapter 5 Technical specifications KFP A Series Installation Manual 121 Figure 28 Small cabinet dimensions and views...
Страница 128: ...Chapter 5 Technical specifications 122 KFP A Series Installation Manual...
Страница 142: ...Appendix C Menu maps 136 KFP A Series Installation Manual...
Страница 148: ......