Chapter 3: Configuration and commissioning
88
KFP-A Series Installation Manual
6. Select the output Class (Class A or Class B).
The default setting is Class B.
7. Press F4 (Enter), and then press F1 (Back).
8. Press F1 (Save), F3 (Apply), F4 (Discard), or F2 (Exit).
Remember to apply saved settings from the Main menu.
Configurable output types are shown in the table below.
Table 51: Configurable output types
Type
Description
SND (default)
Select this option for a sounder output
FR
Select this option for a fire routing output
FP
Select this option for a fire protection output
PRG
Select this option for program options (see below)
EXTIN
Select this option for an extinguishing output
ALARM
Select this option for an output that activates when the control panel is in
alarm status
FAULT
Select this option for an output that activates when the control panel is in
fault status
TEST
Select this option for an output that activates when the control panel is in
test status
DIS
Select this option for an output that activates when the control panel is in
disable status
To enable or disable a control panel output:
1. Select Field setup from the Main menu.
2. Select Panel I/O configuration.
3. Select Outputs, and then select the output to be enabled or disabled.
Configurable outputs are listed as OUT1, OUT2, etc, the supervised alarm
output is listed as ALM_O, and the supervised fault output is listed as FLT_O.
4. In the Control option, select ENB (enable), DIS (disable), DIS_D (disable in
day mode), or DIS_N (disable in night mode).
5. Press F4 (Enter), and then press F1 (Back).
6. Press F1 (Save), F3 (Apply), F4 (Discard), or F2 (Exit).
Remember to apply saved settings from the Main menu.
Note:
At the installer level, changes to the configuration of a Class A output are
applied to all output pairs used to create the Class A output (OUT1/OUT2, etc.).
This includes enable/disable configuration options. For example, if the OUT1
type is changed to PRG and Group-n changed to 5, then the configuration of the
paired OUT2 is updated automatically to match these settings.
Содержание KFP-AE1(-S)
Страница 1: ...KFP A Series Installation Manual P N 00 3252 501 0003 04 ISS 04MAY15...
Страница 6: ...iv KFP A Series Installation Manual...
Страница 20: ...Chapter 1 Introduction 14 KFP A Series Installation Manual...
Страница 113: ...Chapter 3 Configuration and commissioning KFP A Series Installation Manual 107...
Страница 114: ......
Страница 126: ...Chapter 5 Technical specifications 120 KFP A Series Installation Manual Figure 27 Large cabinet dimensions and views...
Страница 127: ...Chapter 5 Technical specifications KFP A Series Installation Manual 121 Figure 28 Small cabinet dimensions and views...
Страница 128: ...Chapter 5 Technical specifications 122 KFP A Series Installation Manual...
Страница 142: ...Appendix C Menu maps 136 KFP A Series Installation Manual...
Страница 148: ......