Chapter 3: Configuration and commissioning
82
KFP-A Series Installation Manual
To change the zone configuration settings:
1. Select Field setup from the Main menu, and then Zone configuration.
2. Select Zone configuration, and then select the corresponding zone from the
list of zones displayed.
3. Make the required configuration changes.
4. Press F4 (Enter), and then press F1 (Back).
5. Press F1 (Save), F3 (Apply), F4 (Discard), or F2 (Exit).
Remember to apply saved settings from the Main menu.
Note:
If all the devices assigned to a zone are disabled, then the zone is
considered to be disabled and is indicated accordingly on the control panel.
Zone alarm confirmation
Zone confirmation is an alarm coincidence configuration method designed to
reduce nuisance alarms. A first alarm event places the zone and the control
panel into alert status. Full alarm status is not confirmed until a second alarm is
reported in the same zone or in a configured area. See “Area configuration” on
page 84 for more information on areas.
Zone alarm confirmation types and descriptions are shown below.
Table 45: Zone alarm confirmation types
Option
Description
NML (default)
No confirmation is required.
sD(A) (type A EN 54-2)
The alarm is confirmed by the same detector. Alarms generated
by a manual call point are not confirmed and activate a control
panel alarm immediately.
aDsZ (type A EN 54-2)
The alarm is confirmed by the same detector or by a different
detector in the same local zone. Alarms generated by a manual
call point are not confirmed and activate a control panel alarm
immediately.
dDsZ (type A EN 54-2)
The alarm is confirmed by a different detector in the same local
zone. Alarms generated by a manual call point are not
confirmed and activate a control panel alarm immediately.
aDMsZ
The alarm is confirmed by a single manual call point and a
single detector in the same local zone irrespective of which
device first reports the alarm event.
aIMsZ
The alarm is confirmed by a single manual call point and a
single initiating device in the same local zone irrespective of
which device first reports the alarm event.
dMsZ
The alarm is confirmed by two different manual call points in the
same local zone irrespective of which device first reports the
alarm event. A detector alarm places the zone in alert status.
Содержание KFP-AE1(-S)
Страница 1: ...KFP A Series Installation Manual P N 00 3252 501 0003 04 ISS 04MAY15...
Страница 6: ...iv KFP A Series Installation Manual...
Страница 20: ...Chapter 1 Introduction 14 KFP A Series Installation Manual...
Страница 113: ...Chapter 3 Configuration and commissioning KFP A Series Installation Manual 107...
Страница 114: ......
Страница 126: ...Chapter 5 Technical specifications 120 KFP A Series Installation Manual Figure 27 Large cabinet dimensions and views...
Страница 127: ...Chapter 5 Technical specifications KFP A Series Installation Manual 121 Figure 28 Small cabinet dimensions and views...
Страница 128: ...Chapter 5 Technical specifications 122 KFP A Series Installation Manual...
Страница 142: ...Appendix C Menu maps 136 KFP A Series Installation Manual...
Страница 148: ......