Chapter 2: Installation
32
KFP-A Series Installation Manual
Figure 16: Selecting 115 or 230 VAC operation
Connecting the batteries
The control panel requires two 12 V, rechargeable, sealed lead-acid batteries
with 7.2, 12, or 18 Ah capacity (see “Battery maintenance” on page 111).
Batteries are located inside the control panel cabinet and must be installed in
series. Polarity must be observed.
Connect batteries to the BAT connector on the control panel PCB. No other
equipment may be connected to the BAT connector.
Note:
If the control panel indicates a Supply Fault, then the batteries may need
to be replaced.
Connecting expansion boards
Caution:
Always disconnect the control panel from the mains power supply
before installing an expansion board.
See your expansion board installation sheet for detailed installation information.
Connecting a fire network
Note:
See your network board installation sheet for detailed installation and
connection information.
Each network board has two ports. Each port is connected (point to point) to the
corresponding ports of the network board in another control panel.
Figure 17: Network board connections
Содержание KFP-AE1(-S)
Страница 1: ...KFP A Series Installation Manual P N 00 3252 501 0003 04 ISS 04MAY15...
Страница 6: ...iv KFP A Series Installation Manual...
Страница 20: ...Chapter 1 Introduction 14 KFP A Series Installation Manual...
Страница 113: ...Chapter 3 Configuration and commissioning KFP A Series Installation Manual 107...
Страница 114: ......
Страница 126: ...Chapter 5 Technical specifications 120 KFP A Series Installation Manual Figure 27 Large cabinet dimensions and views...
Страница 127: ...Chapter 5 Technical specifications KFP A Series Installation Manual 121 Figure 28 Small cabinet dimensions and views...
Страница 128: ...Chapter 5 Technical specifications 122 KFP A Series Installation Manual...
Страница 142: ...Appendix C Menu maps 136 KFP A Series Installation Manual...
Страница 148: ......