Chapter 1: Introduction
10
KFP-A Series Installation Manual
There are two fire routing output groups, the first is in activated status and the
second is in acknowledged status. The fire routing indication displays the
acknowledged status but not the activation status (the acknowledgement status
takes priority).
For more information on output groups, see “Output groups” on page 89.
LCD controls and indicators
Figure 3: LCD controls and indicators
1. Day/night mode indicator
2. System date and time (and active fire routing delay or extended fire routing delay countdown)
3. Control panel network status (stand-alone, networked, repeater)
4. Current alarm, fault, and condition events counter
5. Message display area
6. Soft keys (menu options linked to function buttons F1, F2, F3, and F4)
7. Jog dial
8. Function buttons F1, F2, F3, and F4
9. Local control panel ID (in a fire network)
Содержание KFP-AE1(-S)
Страница 1: ...KFP A Series Installation Manual P N 00 3252 501 0003 04 ISS 04MAY15...
Страница 6: ...iv KFP A Series Installation Manual...
Страница 20: ...Chapter 1 Introduction 14 KFP A Series Installation Manual...
Страница 113: ...Chapter 3 Configuration and commissioning KFP A Series Installation Manual 107...
Страница 114: ......
Страница 126: ...Chapter 5 Technical specifications 120 KFP A Series Installation Manual Figure 27 Large cabinet dimensions and views...
Страница 127: ...Chapter 5 Technical specifications KFP A Series Installation Manual 121 Figure 28 Small cabinet dimensions and views...
Страница 128: ...Chapter 5 Technical specifications 122 KFP A Series Installation Manual...
Страница 142: ...Appendix C Menu maps 136 KFP A Series Installation Manual...
Страница 148: ......