290
16.42.3.2
Wiring for cable connections using
SIMATIC TI505 Series CPU’s
with RS232 D-Sub Male Socket
ports.
KEP Part#: (Not Available) (D-Sub 9 Male Socket to D-Sub 9 Female Plug Cable)
HMI PLC[RS-232]
Connect to SIMATIC TI505 Series with RS232 Port
2 TXD
Æ
2 RXD
3 RXD
Æ
3 TXD
5 GND
Æ
5 GND
7 RTS
Æ
8 CTS
1 DCD
Æ
4 DTR
Æ
6 DSR
Shield
Æ
Earth Ground
16.42.3.3
Wiring for cable connections using
SIMATIC TI555 CPU/545-1102 CPU’s
with RS232 D-Sub Male
Socket ports.
KEP Part#: (Not Available) (D-Sub 9 Female Plug to D-Sub 9 Female Plug Cable)
HMI PLC[RS-485]
Connect to SIMATIC TI555 CPU/545-1102 with RS-422 port
1 RXD-
Æ
8 DO-
2 RXD+
Æ
3 DO+
3 TXD-
Æ
2 DI-
4 TXD+
Æ
9 DI+
5 GND
Æ
5 GND
Shield
Æ
Earth Ground
Note:
Graphic representation may not reflect the actual appearance of the finished cable.
16.42.4 Device address
Bit/Word
Type
Address Format
Range
Notes
B
CR
ddddd
ddddd: 1~65535
Internal Relay
B
X
ddddd
ddddd: 1~65535
Input Coils
B
Y
ddddd
ddddd: 1~65535
Output Coils
W
V
ddddd
ddddd: 1~65535
Data words
W
STW
ddddd
ddddd: 1~65535
Status Words
W
TCP
ddddd
ddddd: 1~65535
Timer/Counter Presets
W
TCC
ddddd
ddddd: 1~65535
Timer/Counter Accumulators
W
WX
ddddd
ddddd: 1~65535
Input Coils as Words
W
WY
ddddd
ddddd: 1~65535
Output Coils as Words