16.14 IIS ESC (INDUSTRIAL INDEXING SYSTEMS)
16.14.1 HMI Setting
Communication parameters must be set the same as those of the PLC. The following settings are recommended.
Parameter
Recommended Setting
Notes
Serial I/F port
RS232
Options: RS232, RS485 – Dependant on PLC hardware
Baud rate
19200
Options: 9600, 19200, 38400, 57600, 115200 - Must match PLC port
setting
Parity
None
Options: Odd, Even, None - Must match PLC port setting
Data bits
8
Options: 7, 8 - Must match PLC port setting
Stop bits
1
Options: 1, 2 - Must match PLC port setting
HMI station No.
0
Not used
PLC station No.
255
Not used
Comm. delay (10msec) 0
Request delay: 0~999 @10 milliseconds. Use when the PLC requires a
delay between requests. Not implemented in simulation mode.
16.14.2 Controller Setting
Communication parameters must be the same as those of the MMI.
App Port set Mode: ESC Packet Protocol 19200, None, 8, 1
Compatible PLC
Emerald EMC-2000 controller
16.14.3 Wiring
16.14.3.1
Wiring for cable connections using
Emerald EMC-2000 Controllers
with RS232 RJ-12 socket ports.
KEP Part#: (Not Available) (D-Sub 9 Male Socket to RJ-12 Male Cable)
HMI PLC[RS-232]
Connect to Emerald EMC-2000 Controller
with RS232 Port
2 TXD
Æ
3 RXD
3 RXD
Æ
5 TXD
5 GND
Æ
4 GND
Shield
Æ
Earth Ground
Note:
Graphic representation may not reflect the actual appearance of the finished cable.