Appendix C.1. Specifications
Appendix C.1.1. Compliance with UL Regulations
For UL compliance, the following instructions must be met when operating COM CARD.
•
The units shall be powered by listed LPS or Class 2 power supply suited to the expected
operating temperature range.
•
The interconnecting power connector and power cable shall:
o
Comply with local electrical code
o
Be suited to the expected operating temperature range
o
Meet the current and voltage rating for COM CARD
•
Furthermore, the interconnecting power cable shall:
o
Be
of length not exceeding 3.05m (118.3”)
o
Be constructed of materials rated VW-1, FT-1 or better
•
If the unit is to be installed in an operating environment with a temperature above 65 °C, it should be
installed in a Restricted Access Area requiring a key or a special tool to gain access.
•
This device must not be connected to a LAN segment with outdoor wiring.
COM CARD Option 3
COM CARD Option 4
Electrical Connections
One 3-pin Phoenix connector with
RS-485 port (+ / - / gnd)
One Ethernet 10/100 BaseT port
One 2-pin Phoenix connector with:
One FTT-10 LonWorks port
One Ethernet 10/100 BaseT port
Approvals
CE Certified; TUV approved to UL 916, EN 60950-1,
EN 50491-3 and CSA C22-2 standards; FCC Class A Part 15;
DNP 3.0 Conformance Tested; RoHS Compliant; CSA 205 Approved
BTL Marked
LonMark Certified
Power Requirements
5V DC
Physical Dimensions
6.9 x 3.0 x 2.0 cm
2.7 x 1.2 x 0.8 in.
8.5 x 3.0 x 2.0 cm
3.3 x 1.2 x .08 in.
Weight
0.03 kg (0.07 lbs)
Operating Temperature
-40°C to 75°C (-40°F to167°F)
Surge Suppression
EN61000-4-2 ESD EN61000-4-3 EMC EN61000-4-4 EFT
Humidity
5 - 90% RH (non-condensing)
(Specifications subject to change without notice)
Figure 26: Specifications