KEP Multi-Protocol Communication Card Option Start-up Guide
Page 37
Appendix B.3. LEVELtrol_II Modbus RTU Mappings to BACnet, Metasys N2, EtherNet/IP, DF1,
Modbus TCP/IP and LonWorks
Point Name
BACnet
Object
Type
BACnet
Object ID
Metasys
N2 Data
Type
Metasys
N2
Address
EIP Tag Name
DF1
Address
LonWorks Name
LonWorks
SNVT
Level
AI
1
AI
1
Flt_XXX[000]
F11:000
nvoLevel_XXX
SNVT_count_f
Total
AI
2
AI
2
Flt_XXX[002]
F11:002
nvoTotal_XXX
SNVT_count_f
Grand Total
AI
3
AI
3
Flt_XXX[003]
F11:003
nvoGrandTot_XXX
SNVT_count_f
Temperature
AI
4
AI
4
Flt_XXX[004]
F11:004
nvoTemp_XXX
SNVT_count_f
Density
AI
5
AI
5
Flt_XXX[005]
F11:005
nvoDensity_XXX
SNVT_count_f
Preset 1
AV
6
AO
6
Flt_XXX[006]
F11:006
nviPreset1_XXX
SNVT_count_f
Preset 2
AV
7
AO
7
Flt_XXX[007]
F11:007
nviPreset2_XXX
SNVT_count_f
Preset 3
AV
8
AO
8
Flt_XXX[008]
F11:008
nviPreset3_XXX
SNVT_count_f
Preset 4
AV
9
AO
9
Flt_XXX[009]
F11:009
nviPreset4_XXX
SNVT_count_f
Year
AI
10
AI
10
U16_XXX[020] N10:020
nvoYear_XXX
SNVT_count_f
Month
AI
11
AI
11
U16_XXX[021] N10:021
nvoMonth_XXX
SNVT_count_f
Day
AI
12
AI
12
U16_XXX[022] N10:022
nvoDay_XXX
SNVT_count_f
Hours
AI
13
AI
13
U16_XXX[023] N10:023
nvoHours_XXX
SNVT_count_f
Minutes
AI
14
AI
14
U16_XXX[024] N10:024
nvoMinutes_XXX
SNVT_count_f
Seconds
AI
15
AI
15
U16_XXX[025] N10:025
nvoSeconds_XXX
SNVT_count_f
Transaction Number
AI
16
AI
16
U16_XXX[028] N10:028
nvoTransNum_XXX
SNVT_count_f
Error-Pulse Out Overflow
BI
1
DI
1
Bit_XXX[000] B12:000
nvoPlsOutOvr_XXX
SNVT_switch
Error-A to D Not Converting
BI
2
DI
2
Bit_XXX[022] B12:022
nvoAtDNtConv_XXX
SNVT_switch
Error-Aux Input Too Low
BI
3
DI
3
Bit_XXX[023] B12:023
nvoAuxIn2Lo_XXX
SNVT_switch
Error-Aux Input Too High
BI
4
DI
4
Bit_XXX[024] B12:024
nvoAuxIn2Hi_XXX
SNVT_switch
Error-Level Input Too Low
BI
5
DI
5
Bit_XXX[025] B12:025
nvoLvlIn2Lo_XXX
SNVT_switch
Error-Level Input Too High
BI
6
DI
6
Bit_XXX[026] B12:026
nvoLvlIn2Hi_XXX
SNVT_switch
Error-RTD Out Of Range
BI
7
DI
7
Bit_XXX[028] B12:028 nvoRTDOutRng_XXX SNVT_switch
Warning-Battery Low Warning
BI
8
DI
8
Bit_XXX[029] B12:029
nvoBattLoWrn_XXX
SNVT_switch
Command-Reset Errors
BV
9
DO
9
Bit_XXX[033] B12:033
nviResErr_XXX
SNVT_switch
Command-Print Command
BV
10
DO
10
Bit_XXX[034] B12:034
nviPrintCmd_XXX
SNVT_switch
Status-Instr Type Rate/Total or Batch
BI
11
DI
11
Bit_XXX[035] B12:035
nvoInsTypRt_XXX
SNVT_switch
Command-Start Batch Command
BV
12
DO
12
Bit_XXX[036] B12:036
nviSttBtcCmd_XXX
SNVT_switch
Command-Stop Batch Command
BV
13
DO
13
Bit_XXX[037] B12:037
nviStpBtcCmd_XXX
SNVT_switch
Command-Clear Batch Command
BV
14
DO
14
Bit_XXX[038] B12:038
nviClrBtcCmd_XXX
SNVT_switch
Status-Batch Filling Status
BI
15
DI
15
Bit_XXX[039] B12:039
nvoBtcFillSt_XXX
SNVT_switch
Status-Batch Stopped Status
BI
16
DI
16
Bit_XXX[040] B12:040
nvoBtcStopSt_XXX
SNVT_switch
Status-Batch Idle Status
BI
17
DI
17
Bit_XXX[041] B12:041
nvoBtcIdleSt_XXX
SNVT_switch
Status-Relay 1 Status
BI
18
DI
18
Bit_XXX[046] B12:046
nvoRel1Stat_XXX
SNVT_switch
Status-Relay 2 Status
BI
19
DI
19
Bit_XXX[047] B12:047
nvoRel2Stat_XXX
SNVT_switch
Status-Relay 3 Status
BI
20
DI
20
Bit_XXX[048] B12:048
nvoRel3Stat_XXX
SNVT_switch
Status-Relay 4 Status
BI
21
DI
21
Bit_XXX[049] B12:049
nvoRel4Stat_XXX
SNVT_switch
Status-Control 1 Status
BI
22
DI
22
Bit_XXX[050] B12:050
nvoCtrl1Stat_XXX
SNVT_switch
Status-Control 2 Status
BI
23
DI
23
Bit_XXX[051] B12:051
nvoCtrl2Stat_XXX
SNVT_switch
Status-Control 3 Status
BI
24
DI
24
Bit_XXX[052] B12:052
nvoCtrl3Stat_XXX
SNVT_switch