background image

 

 

27

Connecting to the Fire Control Instruments 7100 

Serial data connections are made to the FCI 7100 basic system module (BSM) RJ11 RS232 port. 
Connection to the RJ11 RS232 supervision pin (SUPV) permits the 7100 to supervise the cable 
connection and is optional. 

 
As there are no control signals available in 
the 7100 RJ11 connector, the SDACT 
cannot supervise the cable connection. 
Remove user jumper J4 to prevent a serial 
port trouble condition.

 

RTS and CTS pin numbers depend on J1 and J2 jumper settings. The factory default is RTS on Pin 7, CTS on Pin 8. 

IMPORTANT: The 7100 baud rate must be 9600 baud. 

See Appendix A for information on the SIA event codes and zone numbers used by SDACT when 
transmitting 7100 events. 

Local Trouble Annunciation 

For on premises annunciation of S/FDACT trouble conditions, connect the S/FDACT Trouble Relay 
contacts to the 7100 panel by means of an FCI AMM-2 Monitor Module or equivalent. The AMM-2 is an 
addressable dry-contact monitoring module compatible with the 7100 Signaling Line Circuits. The 
AMM-2 is mounted in a standard electrical box adjacent to the S/FDACT enclosure. 

 

Connect the S/FDACT Trouble Relay Normally Open contact, terminal 22, to the AMM-2 violet 
wire. 

 

Connect the S/FDACT Trouble Relay Common contact, terminal 21, to the AMM-2 yellow wire. 

 

Make sure to install the 4.7K EOL resistor included with the AMM-2. 

 

Wire the AMM-2 red and black wires to the 7100’s signaling line circuit according to instructions 
provided in the 7100 installation manual. 

 

Set the AMM-2 rotary switches to the address range 50 – 59 to configure it for a non-latching 
trouble function. S/FDACT trouble conditions will result in an Off Normal signal at the 7100 
panel. 

7100 RJ11 Connector of BSM 
SDACT DB9 Pin 

7100 RJ11 Pin 

RD 3  5 TXD 

SG 5 3,4 

GND 

RTS 

7 (or 8)

6 (optional) 

SUPV 

Содержание FDACT

Страница 1: ...User s Manual for Keltron SDACT and FDACT Fire Dialers Keltron Corporation 101A First Avenue Waltham MA 02451 Voice 781 894 8710 fax 781 899 9652 SFDACT DOC Rev 2 2 11 1 06 626 2104 P N 92MSDACT ...

Страница 2: ......

Страница 3: ...tallation Overview 19 Selecting a Location 19 Wall Mounting 19 Field Wiring Power Supply Connections 20 Field Wiring Supervised Hardwired Alarm Zones 22 Field Wiring Power Monitor Zones 23 Field Wiring Telephone Line Connections 24 Field Wiring FACP Serial Data Connections 26 SDACT Field Wiring Connection Diagram 31 Chapter 4 Installation Programming 33 Set Event Codes 33 Set Telephone Numbers 35 ...

Страница 4: ......

Страница 5: ... is operating properly and can successfully report an alarm the fire dialer must be tested immediately after installation and periodically thereafter according NFPA 72 Chapter 10 and the enclosed test instructions Note System Re acceptance Test after Software Changes To ensure proper system operation this product must be tested in accordance with NFPA 72 Chapter 10 after any programming operation ...

Страница 6: ......

Страница 7: ...gnals such as fire trouble water flow or supervisory can be reliably transmitted These signals are typically provided by the general alarm general trouble etc relay contact outputs of the FACP In addition the SDACT serial port monitors FACP serial data which is normally intended for a local printer or CRT display That data includes point specific information such as detector type and address and u...

Страница 8: ...rm and general trouble contact outputs The alarm output indicates serial port derived events that are pending transmission and input zone activations The trouble output indicates telephone line faults communicator faults serial port faults as well as input zone and power faults These outputs may be monitored or simply provide local fault indications Features The Keltron SDACT contains a powerful m...

Страница 9: ...uble and alarm with 24 hour trouble resound Line seizure is provided for use with shared phone lines as allowed by the local authority having jurisdiction A manual test button is included A silence pushbutton deactivates the on board audible signal A program pushbutton invokes the programming session A CPU reset button resides on board Local LED s and audible devices clearly indicate S FDACT statu...

Страница 10: ...For products approved after July 23 2001 the REN for this product is part of the product identifier that has the format US AAAEQ TXXXX The digits represented by are the REN without a decimal point e g 03 is a REN of 0 3 For earlier products the REN is separately shown on the label If the Keltron SDACT or FDACT compromises your telephone network the telephone company will notify you in advance that...

Страница 11: ... alarm zone inputs is required for UL Listed installations remotely monitoring FACP S via the Public Switched Telephone Network To indicate the supplementary and or redundant nature of the serial data information at the receiving station all serial port events SDACT only are transmitted as old events or SIA O blocks The SDACT and FDACT are not suitable for the direct monitoring of sprinkler superv...

Страница 12: ...ACTBX Listed Signaling Device Enclosure 4 10K EOL resistors P N 64K3355 10K 2 Modular patch cords P N 63RJ4507 1 Programming utility CD P N SDSFDPrgmr 1 Printed user manual P N 92MSDACT For SDACT only one of the following personality software modules will be factory installed FCI 7100 P N 97P1081SD FCI 7200 P N 97P1082SD Edwards EST2 P N 97P1041SD Mirtone MIR2 P N 97P1211SD ...

Страница 13: ... with conduit knockouts Hinged front access door with key lock all keyed alike Size 14 H x 17 W x 4 D Weight 12 lbs Environmental specifications Relative humidity 0 to 93 non condensing Operating temperature 0 to 49o C Storage temperature 10 to 60 o C This device is suitable for dry indoor use only This device is suitable for use in a non corrosive environment only Functional specifications Config...

Страница 14: ...m zone status 4 red 4 yellow 2 Serial port status 1 red 1 yellow 4 Telephone line status 2 red 2 yellow 2 Relay output status red Audible 92 DB pulsed for alarm steady for trouble User pushbuttons 4 reset test program silence User jumpers 8 2 Serial port handshake configuration 1 Audible enable 1 Serial port supervision enable 3 Power monitor zone configuration 1 AC power failure transmission dela...

Страница 15: ...alarm relay energizes and the alarm contact active LED illuminates The audible device sounds the pulsed alarm signal The corresponding event code See appendix A is transferred to the SIA transmitter see dialing operation for transmission as an old event using a SIA O block If the corresponding event code represents an AC Power Failure message from the FACP and if User Jumper J8 is installed then t...

Страница 16: ...peration If User Jumper J8 is installed then an off normal status change on the AC failure zone 5 will illuminate the power fault LED but the trouble relay local audible and the AC Power Failure transmission are delayed for 2 hours If zone 5 restores to normal before the 2 hours elapses the pending AC Power Failure transmission and the Restore transmission are cancelled If zone 5 restores to norma...

Страница 17: ...one line fault is detected The Telco fault LED for that line illuminates The common trouble relay energizes and the trouble contact active LED illuminates The audible device sounds the steady trouble signal The programmed or default LT line trouble event code is transferred to the SIA transmitter see dialing operation The silence pushbutton may be used to silence the audible The audible will autom...

Страница 18: ...ble in 24 hours if the trouble condition is still present Configuration Trouble The Keltron S FDACT stores user programmable settings in non volatile EEPROM memory The content of this memory is checked for integrity at power up or reset and whenever a new user configuration is programmed If the configuration memory becomes corrupted the S FDACT cannot perform any dialer functions since the stored ...

Страница 19: ...low battery zone 6 or no missing battery zone 7 power monitor zone inputs If all of the power monitor zones are normal the power fault LED goes out If no other monitored conditions require the common trouble relay to be active it returns to its normal state and the trouble contact active LED goes out If no other monitored conditions require the audible to be active the audible is silenced The prog...

Страница 20: ...A transmitter where is 1 for the primary telephone number and 2 for the secondary telephone number see dialing operation Daily Test Operation If the Keltron S FDACT is configured for 24 hour daily test interval factory default the daily test transmission will be sent once per day at the programmed or default midnight daily test time If the S FDACT is configured for 4 hour daily test interval the t...

Страница 21: ...tion DACR i e the S FDACT will pause sufficient time to receive a dial tone but does not require a dial tone to start dialing The S FDACT always dials using dual tone multi frequency DTMF tones Please consult the factory for pulse or rotary dialing applications Sequence of Telephone Call Attempts Assuming no call attempts are successful the Keltron S FDACT will try a total of eight times to comple...

Страница 22: ...onnect the FACP and connect the serial port to his PC or laptop While in programming mode the red and yellow serial port LEDS will alternately light once a second as an indication that programming mode is active If there is no serial port activity for 60 seconds the S FDACT will time out and resume normal monitoring mode Pressing the test pushbutton also causes immediate return to normal monitorin...

Страница 23: ...port SDACT only J4 should be set appropriately for the specific FACP being monitored See Serial Port Installation notes J5 J6 and J7 set the normal condition of the power monitor zones 5 6 and 7 respectively Jumper installed sets the zone to normally open Jumper removed sets the zone to normally closed The factory default is all zones normally open J8 configures the transmission delay for AC power...

Страница 24: ...18 ...

Страница 25: ...lecting a Location The Keltron S FDACT may be installed in any environment which would be comfortable for a human being Typically the S FDACT will be installed in the same room as the FACP which it is monitoring Please read the environmental specifications for details In addition Do not mount on exterior walls especially masonry walls Do not mount directly on exterior walls below grade Protect fro...

Страница 26: ... must include the S FDACT load current in the FACP s battery calculations Connect the 24 VDC supply making sure to observe the correct polarity Connect the positive lead to terminal 15 Connect the return lead Common to terminal 16 Caution reversing the polarity for long periods of time can damage both the unit and the power source The S FDACT is protected by a diode in series with the power input ...

Страница 27: ... the PSU SPSU terminal TB1 3 or TB1 4 Using the Edwards System Technology EST2 Aux Power Output The EST2 s 24 VDC non resettable auxiliary power circuit is compatible with the S FDACT Connect S FDACT terminal 15 24 to the EST2 PPS terminal TB3 SMK AUX PWR and connect S FDACT terminal 16 C to the PPS terminal TB3 SMK AUX PWR Install PPS jumper JP4 to set the AUX PWR output to non resettable Using t...

Страница 28: ...allel at the monitored device Four EOLRs are provided for this purpose Keltron part number 64K3355 10K Connections to the alarm zones are as shown above Input zones are sampled every 62mS Changes must be present for 8 consecutive samples to pass debounce This gives each zone a 500mS response time IMPORTANT The hardwired alarm zones are the primary means of alarm signaling via Keltron s SDACT and F...

Страница 29: ...t zones 5 6 and 7 may be used as external power source monitor input circuits Each zone is independently configurable for either normally open or normally closed dry contact programmable activation These zones are considered supplementary and unsupervised ...

Страница 30: ...elephone Line Connection The Keltron SDACT and FDACT are alarm dialing equipment and must be able to seize the telephone line and place a call in an emergency situation They must be able to do this even if other equipment telephone answering system computer modem etc already has the telephone line in use To do so alarm dialing equipment must be connected to a properly installed RJ31X jack that is ...

Страница 31: ...507 Plug one end of the modular cord into the S FDACT RJ 45 jack Plug the other end into the RJ31X jack For reference proper wiring of the RJ31X jack is shown in the figure below The S FDACT is electrically isolated from the telephone lines so that a ground fault on a telephone line does not fault the S FDACT and the S FDACT complies with FCC requirements Each telephone line interface circuit of t...

Страница 32: ...TS or CTS set by J1 and J2 8 CTS or RTS set by J1 and J2 9 No connection IMPORTANT The FACP serial data connections provide supplementary alarm information only Use of the hardwired alarm zone inputs is required as the primary means of alarm signaling for UL Listed installations monitoring FACP S for Remote Station Central Station and Proprietary service To indicate the supplementary and or redund...

Страница 33: ...tions connect the S FDACT Trouble Relay contacts to the 7100 panel by means of an FCI AMM 2 Monitor Module or equivalent The AMM 2 is an addressable dry contact monitoring module compatible with the 7100 Signaling Line Circuits The AMM 2 is mounted in a standard electrical box adjacent to the S FDACT enclosure Connect the S FDACT Trouble Relay Normally Open contact terminal 22 to the AMM 2 violet ...

Страница 34: ...ard electrical box adjacent to the S FDACT enclosure Connect the S FDACT Trouble Relay Normally Open contact terminal 22 to the AMM 2 violet wire Connect the S FDACT Trouble Relay Common contact terminal 21 to the AMM 2 yellow wire Make sure to install the 4 7K EOL resistor included with the AMM 2 Wire the AMM 2 red and black wires to the 7200 s ALU signaling line circuits according to instruction...

Страница 35: ...ACT when transmitting EST2 events Local Trouble Annunciation For on premises annunciation of S FDACT trouble conditions connect the S FDACT Trouble Relay contacts to the EST2 panel by means of a Signature Series SIGA CT1 Single Input Module or equivalent The SIGA CT1 is an addressable dry contact monitoring module compatible with the EST2 Signature Loop Controller The SIGA CT1 is mounted in a stan...

Страница 36: ...when transmitting MIR2 events Local Trouble Annunciation For on premises annunciation of S FDACT trouble conditions connect the S FDACT Trouble Relay contacts to the MIR2 panel by means of a Signature Series GSA CT1 Single Input Module or equivalent The GSA CT1 is an addressable dry contact monitoring module compatible with the MIR2 Signature Data Circuit The GSA CT1 is mounted in a standard elect...

Страница 37: ...31 SDACT Field Wiring Connection Diagram ...

Страница 38: ...32 ...

Страница 39: ...no delay 1 3 hours The S FDACT programmer is a Windows PC application SFDPrgmr exe to configure an SDACT or FDACT for use The S FDACT programmer is compatible with Windows XP Windows 2000 Windows NT and Windows 98 In many cases the factory default settings for your S FDACT will be used but at a minimum you must program the telephone numbers of the intended receiving stations You ll probably also w...

Страница 40: ... Trouble Restore Power Monitor Tab As shown in the figure below the power monitor tab is used to set the event codes for the three unsupervised power monitor zones The AC power monitor input zone 5 has a programmable fault code and restore code The low battery input zone 6 and the missing battery input zone 7 each have a programmable fault code but there is a common restore code The factory defaul...

Страница 41: ... manual test Set Telephone Numbers These boxes are used to set the primary and secondary telephone numbers that S FDACT will dial when reporting Both must be set before uploading the configuration to the S FDACT Up to 20 digits or characters may be entered for each telephone number The comma character is the SIA standard character for a two second pause during dialing Each comma counts as one tele...

Страница 42: ... Set Options Telephone Lines Used The default setting is for S FDACT to use and supervise both of its telephone line connections If a second telephone line is not available checking the line 1 only option will prevent S FDACT from reporting a line fault condition on line 2 Send Troubles to Second Account Normally the Keltron S FDACT will send all reports to the primary account i e the primary tele...

Страница 43: ... sync time mode and any values you entered for the date and time will be overwritten by current values from your PC s clock Set Date and Set Time Use these boxes to manually set the date and time to be programmed into the S FDACT These boxes are disabled in auto sync time mode Download Date Time from S FDACT This control allows you to check the current value of the real time clock and calendar in ...

Страница 44: ...pen a previously saved S FDACT configuration file Save Saves the current configuration settings to the previously opened file If no file was opened previously it displays a standard Windows file save as dialog to save the current configuration settings to a file Save As Displays a standard Windows file save as dialog to save the current configuration settings to a file Exit Closes the open comm po...

Страница 45: ... 8 After the S FDACT has reported the zone restore to normal the S FDACT should return to the idle all normal state Troubleshooting In case of trouble Check for the proper power input with sufficient voltage and current Ensure the input voltage does not drop below rated limits when the Keltron S FDACT is activated for phone line signal transmission Observe the condition of all trouble LED s and re...

Страница 46: ...on Corporation 101A First Avenue Waltham Massachusetts 02451 Telephone 781 894 8710 Toll Free 800 966 6123 FAX 781 899 9652 Email info keltroncorp com GENERAL Telephone 781 894 8710 Email info keltroncorp com SALES Telephone 781 894 8710 ext 2054 Email sales keltroncorp com SUPPORT SERVICES Telephone 781 894 8710 ext 2077 Email support keltroncorp com Keltron develops and manufactures secure relia...

Страница 47: ... improper installation or application The warranty does not extend to products that have been repaired or altered outside our factory without our written approval Except as provided above Keltron Corporation makes no warranty of any kind express or implied except that the goods sold under this agreement shall be of the standard quality of Keltron Corporation and the buyer assumes all risk and liab...

Страница 48: ...42 ...

Страница 49: ...e only and do not network more than 15 panels Otherwise ambiguous SIA Zone numbers will result Also please verify that the central station receiver and central station automation computer are compatible with 4 digit SIA Zone numbers 3 Digit Option This option is available for central stations that are NOT compatible with 4 digit zone numbers With this option the zone numbers are always reported in...

Страница 50: ...y FV Fire Supervision Restoral MLT EVENTS UA Untyped Zone Alarm UH Untyped Alarm Restore SHORT DISCONNECT MISSING WRONG TYPE EXTRA ADDR CONFIG ERR LOOP BREAK FT Fire Trouble FR Fire Restoral TEST FAIL DIRTY VERY DIRTY AS Analog Service Needed AN Analog Restoral OUTPT FAIL YA Bell Fault Output Trouble YH Bell Restoral AC FLT TO AT AC Trouble AR AC Restoral FAULT TALLY FLT EEPROM BAD YX Service Requ...

Страница 51: ...s added to the field programmed account numbers For example if the programmed account number is 1000 then events from unit number 1 ALU1 QZU1 EZU1 report on account 1000 Events from unit number 2 will report on account 1001 and events from unit number F will report on account 1014 Note that the 3 Digit Option must be specified when ordering your SDACT from the factory It is not a field configurabl...

Страница 52: ...NORMAL FS Fire Supervisory FV Fire Supervision Restoral SHORT CM SHORT DISCONNECT MISSING WRONG TYPE EXTRA ADDR CONFIG ERR TROUBLE LOOP BREAK FT Fire Trouble FR Fire Restoral TEST FAIL DIRTY VERY DIRTY AS Analog Service Needed AN Analog Restoral UNEXPECTED YA Bell Fault Output Trouble YH Bell Restoral COMM FAULT YC Communications Fail YK Communications Restoral FAULT YX Service Required YZ Service...

Страница 53: ...s No conversion is necessary for the detectors modules and notification appliance circuit point IDs Those point IDs are transmitted directly as the 4 digit SIA zone number The EST2 panel fault point IDs are converted to different SIA zone numbers so there is no conflict with the SDACT s hardwired zone numbers The conversion rules are summarized in the following table CATEGORY EST2 POINT SIA ZONE 2...

Страница 54: ...ERVISORY FS Fire Supervisory FV Fire Supervision Restore SHORT FAULT OPEN FAULT FT Fire Trouble FR Fire Restoral OPEN FAULT Battery YT System Battery Trouble YR System Battery Restoral OPEN FAULT Primary Power AT AC Trouble AR AC Restoral MAINTENANCE REQUIRED AS Analog Service Needed AN Analog Restoral COMMUNICATION FAULT YC Communications Fail YK Communications Restoral GROUND FAULT YP Power Supp...

Страница 55: ... is necessary for the detectors modules and notification appliance circuit point IDs Those point IDs are transmitted directly as the 4 digit SIA zone number The MIR2 panel fault point IDs are converted to different SIA zone numbers so there is no conflict with the SDACT s hardwired zone numbers The conversion rules are summarized in the following table CATEGORY MIR2 POINT SIA ZONE MIR2 MCM Detecto...

Страница 56: ...ERVISORY FS Fire Supervisory FV Fire Supervision Restore SHORT FAULT OPEN FAULT FT Fire Trouble FR Fire Restoral OPEN FAULT Battery YT System Battery Trouble YR System Battery Restoral OPEN FAULT Primary Power AT AC Trouble AR AC Restoral MAINTENANCE REQUIRED AS Analog Service Needed AN Analog Restoral COMMUNICATION FAULT YC Communications Fail YK Communications Restoral GROUND FAULT YP Power Supp...

Страница 57: ...n CW Was Force Armed CX Custom Function Executed CZ Point Closing DA Card Assigned DB Card Deleted DC Access Closed DD Access Denied DE Request to Enter DF Door Forced DG Access Granted DH Door Left Open Restoral DI Access Denied Passback DJ Door Forced Trouble DK Access Lockout DL Door Left Open Alarm DM Door Left Open Trouble DN Door Left Open non alarm non trouble DO Access Open DP Access Denie...

Страница 58: ...old JO Log Overflow JP User On Premises JR Schedule Executed JS Schedule Changed JT Time Changed JV User Code Changed JX User Code Deleted JY User Code Added JZ User Level Set KA Heat Alarm KB Heat Bypass KH Heat Alarm Restore KJ Heat Trouble Restore KR Heat Restoral KS Heat Supervisory KT Heat Trouble KU Heat Unbypass LB Local Program LD Local Program Denied LE Listen in Ended LF Listen in Begin ...

Страница 59: ... Alarm SB Sprinkler Bypass SC Change of State SH Sprinkler Alarm Restore SJ Sprinkler Trouble Restore SR Sprinkler Restoral SS Sprinkler Supervisory ST Sprinkler Trouble SU Sprinkler Unbypass TA Tamper Alarm TB Tamper Bypass TC All Points Tested TE Test End TH Tamper Alarm Restore TJ Tamper Trouble Restore TP Walk Test Point TR Tamper Restoral TS Test Start TT Tamper Trouble TU Tamper Unbypass TW ...

Страница 60: ... Trouble YE Receiver Line Card Restored YF Parameter Checksum Fail YG Parameter Changed YH Bell Restored YI Overcurrent Trouble YJ Overcurrent Restore YK Communications Restoral YM System Battery Missing YN Invalid Report YO Unknown Message YP Power Supply Trouble YQ Power Supply Restored YR System Battery Restoral YS Communications Trouble YT System Battery Trouble YU Diagnostic Error YW Watchdog...

Отзывы: