47
Edwards System Technology EST2
The EST2 allocates fixed ranges of 4-digit point IDs to all detectors, modules, and notification appliance
circuits either connected directly to the 2-MCM main controller module or to the 2-LCX Expander
module. In addition the EST2 assigns unique point IDs to various panel faults, for example point 0003 is
assigned to Battery fault and point 0005 is assigned to Ground fault. Please refer to the EST2 System
Operations Manual for a complete list of faults and point IDs.
No conversion is necessary for the detectors, modules, and notification appliance circuit point IDs. Those
point IDs are transmitted directly as the 4-digit SIA zone number. The EST2 panel fault point IDs are
converted to different SIA zone numbers so there is no conflict with the SDACT’s hardwired zone
numbers.
The conversion rules are summarized in the following table:
CATEGORY
EST2 POINT
SIA ZONE
2-MCM Detectors
0101 to 0196
0101 to 0196
2-MCM NAC
0201 to 0202
0201 to 0202
2-MCM Modules
0203 to 0296
0203 to 0296
2-LCX Detectors
0301 to 0396
0301 to 0396
2-LCX NAC
0401 to 0402
0401 to 0402
2-LCX Modules
0403 to 0496
0403 to 0496
Faults
0001 to 0029
0601 to 0629
Faults
xx97 to xx99
0797 to 0799